background image

10                                                                 

Specifications subject to change without notice.                                                                         IM-DHMSHA-02

INSTALLATION TIPS

Ideal installation locations include:

Indoor Unit

• A location where there are no obstacles near the inlet and outlet 

area.

• A location which can bear the weight of the indoor unit.

• Do not install the indoor units near a direct source of heat such as

direct sunlight or a heating appliance.

• A location which provides appropriate clearances (See Fig. 8 — on

page 9.)

INDOOR UNIT INSTALLATION

PRIOR TO INSTALLATION

Before installing the indoor unit, ensure the compatibility with the

outdoor unit using the product data as a reference.

Select the Installation Location:

Before installing the indoor unit, choose an appropriate location.

Use the following standards should help you choose an appropriate 

unit location. Proper installation locations must meet the following 

standards:

1. Good air circulation

2. Convenient drainage

3. Noise from the unit will not disturb others

4. Firm and solid—the location will not vibrate

5. A site strong enough to support the unit’s weight

6. A  location at least 3.28 ft. (1m) from all other electrical devices

(e.g., TV, radio, computer)

7.

DO NOT

 install the unit in the following locations:

a. Near any source of heat, steam, or combustible gas

b. Near flammable items such as curtains or clothing

c. Near any obstacle that might block air circulation

d. Near the doorway

e. In a location subject to direct sunlight

NOTE: Wall Holes (if there is no fixed refrigerant piping): 

While choosing a location, leave ample room for a 

wall hole. Refer to “DRILL HOLE IN WALL FOR 

THE INTERCONNECTING PIPING, DRAIN 

AND WIRING” on page 10 for the connective 

piping step for the signal cable and the refrigerant 

piping that connect the indoor and outdoor units. 

The default position for all piping is the right side 

of the indoor unit (while facing the unit). However, 

the unit can accommodate piping to both the left 

and right sides.

Attach the Mounting Plate to the Wall:

1. Carefully remove the mounting plate, which is attached on the back

of the indoor unit.

2. Using the stencil, determine the wall hole position. The mounting

plate  should  be  located  horizontally  and  level  on  the  wall. All

minimum spacings (See Fig. 8 — on page 9) should be maintained.

3. If the wall is block, brick, concrete or similar material, drill 0.2” (5 

mm) diameter holes and insert the anchors for the appropriate 

mounting screws.

4. Attach the mounting plate to the wall.

Mounting Plate Dimensions

Different model sizes have different mounting plates. Ensure there’s

enough room to mount the indoor unit (See Fig. 8 — on page 9)

The following measurements can be located on these figures:

• Width of mounting plate

• Height of mounting plate

• Width of indoor unit relative to plate

• Height of indoor unit relative to plate

• Recommended position of wall hole (both to the left and right of

mounting plate)

• Relative distances between the screw holes.

Fig. 9 — Mounting Plate Orientation

DRILL HOLE IN WALL FOR THE 

INTERCONNECTING PIPING, DRAIN AND 

WIRING

Refrigerant Line Routing

The refrigerant lines may be routed in any of the four directions

shown in Fig. 11.

For maximum serviceability, it is recommended to have refrigerant

line flare connections and the drain connections on the outside of

the wall that the fan coil will be mounted on.

If piping is going through the back:

1. Determine  the  pipe  hole  position  using  the  mounting  plate  as  a

template. Drill the pipe hole diameter per the values given in Figures 5,

6, and 7. The outside pipe hole is 1/2-in. (13 mm) min. lower than the

inside pipe hole, so it slants slightly downward (see Fig. 10).

Fig. 10 — Drill Holes

If piping is going through the right or left side:

1. Use a small saw blade to carefully remove the corresponding plastic

covering on the side panel and drill the appropriate size hole where

the pipe is entering the wall.

Fig. 11 — Piping Locations

Correct orientation of Mounting Plate

1/2 in. (13 mm)

Min.

INDOOR

OUTDOOR

Pipe holder

Pipe cover

Right piping

Left piping

Pipe cover

Right back piping

Left back piping

1

2

3

4

Summary of Contents for DHMSHA Series

Page 1: ...l models may differ slightly TABLE OF CONTENTS SAFETY CONSIDERATIONS 2 PARTS LIST 3 SYSTEM REQUIREMENTS 4 WIRING 4 DIMENSIONS 5 CLEARANCES 9 INSTALLATION TIPS 10 INDOOR UNIT INSTALLATION 10 ELECTRICAL...

Page 2: ...NGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsaf...

Page 3: ...Part No Part Name Qty 1 Indoor Unit 1 2 Mounting Plate 1 3 Mounting Screw A ST3 9x25 C H 5 4 Anchor 5 5 Air Filter 1 6 Wireless Remote Control 1 7 Wireless Remote Control Holder 1 8 Wireless Remote C...

Page 4: ...es exists a 14 2 stranded shielded wire can be used to replace L2 N and S between outdoor unit and indoor unit landing the shield onto ground in the outdoor unit only NOTE The main power is supplied t...

Page 5: ...08 230V 208 230V 208 230V 208 230V 208 230V Height In mm 11 07 281 11 07 281 11 07 281 12 40 315 13 39 343 13 39 343 13 39 343 Width In mm 33 17 842 33 17 842 33 17 842 38 98 990 46 69 1186 46 69 1186...

Page 6: ...17 360 33 17 842 33 16 842 32 24 819 2 2 56 1 78 45 11 03 280 9 25 235 8 49 216 7 96 202 9 46 240 9 46 240 9 25 235 9 25 235 8 1 206 7 05 179 5 87 149 8 1 206 6 88 175 5 36 136 1 86 47 7 96 202 8 49...

Page 7: ...6 21 158 5 08 129 4 13 105 3 23 82 1 08 27 11 32 287 10 39 264 9 57 243 8 78 223 7 53 191 5 98 152 5 08 129 4 13 105 3 15 80 1 08 27 10 66 271 12 40 315 2 56 65 1 74 44 5 03 128 13 52 343 38 98 990 20...

Page 8: ...24 57 21 63 549 47 01 1194 20 91 531 2 24 57 2 25 57 2 24 57 13 51 343 2 25 57 12 10 307 14 98 380 14 26 362 12 54 319 11 05 281 9 71 247 4 53 115 4 34 110 4 33 110 4 53 115 9 70 246 12 53 318 14 25 3...

Page 9: ...es NOTE The top clearance recommended for proper return airflow is 5 9in 15cm Reduction of this clearance may decrease unit performance This may be reduced to 3 2in 80mm as long as the right and left...

Page 10: ...ides Attach the Mounting Plate to the Wall 1 Carefully remove the mounting plate which is attached on the back of the indoor unit 2 Using the stencil determine the wall hole position The mounting plat...

Page 11: ...iring on Indoor Unit High Wall Unit Size Indoor Fan Max Fuse CB Amp V PH HZ FLA HP Refer to outdoor unit installation instructions Indoor unit powered by the outdoor unit 12K 208 230 1 60 0 33 0 053 9...

Page 12: ...ring cover and close the indoor unit s front cover 10 Piping a Cut the pipe with a pipe cutter at 90 degrees see Fig 16 b Remove the service connection if provided with the unit Fig 16 Pipe Cutting c...

Page 13: ...cket if installed on the wall 1 Use the two screws supplied with the wireless remote control to attach the mounting bracket to the wall in a location selected by the customer and within operating rang...

Page 14: ...is a combination of flashing LEDs on the display panel or the front of the unit Some indoor units display error codes specifying failure modes in the outdoor units If possible always check the diagno...

Reviews: