M-thermal technical manual
– part 3
The purpose of this field setting is to prevent the user from selecting a wrong (i.e., too hot or too
cold) leaving water temperature. Thereto the heating temperature set point range and the cooling
temperature set point range available to the user can be configured.
“
6-0
”
Cooling set point upper limit: Maximum leaving water temperature for cooling operation.
“
6-1
”
Cooling set point lower limit: Minimum leaving water temperature for cooling operation.
“
6-2
”
Heating set point upper limit: Maximum leaving water temperature for heating operation.
“
6-3
”
Heating set point lower limit: Minimum leaving water temperature for heating operation.
“
6-4
”
Sanitary heating set point upper limit: Maximum leaving water temperature for sanitary
heating operation.
“
6-5
”
Sanitary heating set point lower limit: Minimum leaving water temperature for sanitary
heating operation.
■
Others
“
7-0
”
Celsius/Fahrenheit switching:
“
0
”
for Celsius, and
“
1
”
for Fahrenheit.
“
7-1
”
Silent mode running period: Defines the running period of silent mode.
“
7-2
”
Run test function:
“
0
”
for run test function disable, and
“
1
”
for run test function disable.
“
7-3
”
Run test period: Specifies the period of run test.
“
7-4
”
Under floor first time heating function:
“
0
”
for disable and
“
1
”
for enable.
“
7-5
”
Air purge function:
“
0
”
for disable and
“
1
”
for enable.