DM16-01.01.07en
Blanc
On-off
Service manual
27
7.4 Installation for the first time
Air and moisture in the refrigerant system have undesirable effects as below:
●
Pressure in the system rises.
●
Operating current rises.
●
Cooling or heating efficiency drops.
●
Moisture in the refrigerant circuit may freeze and block capillary tubing.
●
Water may lead to corrosion of parts in the refrigerant system.
Therefore, the indoor units and the pipes between indoor and outdoor units must be leak tested
and evacuated to remove gas and moisture from the system.
Gas leak check (Soap water method):
Apply soap water or a liquid neutral detergent on the indoor unit connections or outdoor unit
connections by a soft brush to check for leakage of the connecting points of the piping. If bubbles
come out, the pipes have leakage.
1. Air purging with vacuum pump
1) Completely tighten the flare nuts of the indoor and outdoor units, confirm that both the
2-way and
3-way valves are set to the closed position.
2) Connect the charge hose with the push pin of handle lo to the 3-way valves gas service port.
3) Connect the charge hose of handle hi connection to the vacuum pump.
4) Fully open the handle Lo of the manifold valve.
5) Operate the vacuum pump to evacuate.
6) Make evacuation for 30 minutes and check whether the compound meter indicates -0.1Mpa. If the
meter does not indicate -0.1Mpa after pumping 30 minutes, it should be pumped 20 minutes more.
If the pressure can’t achieve -0.1Mpa after pumping 50 minutes, please check if there are some
leakage points.
Fully close the handle Lo valve of the manifold valve and stop the operation of the vacuum pump.
Confirm that the gauge needle does not move (approximately 5 minutes after turning off the vacuum
pump).
7) Turn the flare nut of the 3-way valves about 45° counterclockwise for 6 or 7seconds after the gas
coming out, then tighten the flare nut again. Make sure the pressure display in the pressure indicator is
a little higher than the atmosphere pressure. Then remove the charge hose from the 3 way valve.
8) Fully open the 2 way valve and 3 way valve and securely tighten the cap of the 3 way valve.
Summary of Contents for Blanc ON-OFF Series
Page 12: ...Blanc On off DM16 01 01 07en 12 Service manual For MSMA1A 07HRN1 MSMA1A 09HRN1...
Page 13: ...DM16 01 01 07en Blanc On off Service manual 13 For MSMA1B 12HRN1 For MSMA1C 18HRN1...
Page 14: ...Blanc On off DM16 01 01 07en 14 Service manual For MSMA1D 24HRN1...
Page 16: ...Blanc On off DM16 01 01 07en 16 Service manual For MOAB02 07HN1 MOAB02 09HN1...
Page 18: ...Blanc On off DM16 01 01 07en 18 Service manual For MOCA02 24HN1...
Page 34: ...Blanc On off DM16 01 01 07en 34 Service manual MSMA1D 24HRN1...
Page 36: ...Blanc On off DM16 01 01 07en 36 Service manual MOCA02 24HN1...
Page 47: ...DM16 01 01 07en Blanc On off Service manual 47 will display the maximum value or minimum value...