MCAC-ATSM-2014-09 Aqua tempo power series tropical air-cooled scroll chiller 50Hz
139
1. Malfunction & protection codes
1.1 MGBT-F25W/RN1, MGBT-D25W/RN1, MGBT-D30W/RN1, MGBT-F30W/RN1
No
,
Code
Trouble
1
E0
Water flow detection error (The third time)
2
E1
Power phase sequence error
3
E2
Communication error
4
E3
Total water outlet temp. sensor error
5
E4
Outlet water temp. sensor error in shell and tube heat exchanger
6
E5
Pipe temp. sensor error in condenser A
7
E6
Pipe temp. sensor error in condenser B
8
E7
Outdoor ambient temp. sensor error or power supply protection
9
E8
Air exhaust temp. sensor error of digital compressor
10
E9
Water flow detection error (The first and second times)
11
EA
Main unit d
etect that auxiliary unit’s quantity have decreased.
12
Eb
Freeze-proof temp. sensor 1 error in double-pipe heat exchanger
13
EC
Wired controller did not find out any on-line module unit.
14
ED
Wired controller and module unit communication error
15
Ed
1-hour consecutive 4-times PE protection happens
16
EE
Wired controller and computer communication error
17
EF
Inlet water temp. sensor error
18
P0
High pressure or air discharge temp. protection error in system A
19
P1
Low pressure protection happens to system A
20
P2
High pressure or air discharge temp. protection in system B
21
P3
Low pressure protection happens to system B
22
P4
Current protection happens to system A
23
P5
Current protection happens to system B
24
P6
Condenser high pressure protection happens to system A
25
P7
Condenser high pressure protection happens to system B
26
P8
Air discharge temp. sensor protection of digital compressor in ystem A
27
P9
Protection of outlet and inlet water temp. difference
28
PA
Low ambient temp. drive-up protection
29
Pb
System freeze-proof protection
30
PE
Low temp. protection of double-pipe heat exchanger
31
F1
Wired controller failure
32
F2
Failure of reduction of wired controller number at parallel connection of multiple wired controller (reserved)
Summary of Contents for Aqua Tempto Power Series
Page 2: ......
Page 58: ...Aqua tempo power series tropical air cooled scroll chiller 50Hz MCAC ATSM 2014 09 56...
Page 61: ...MCAC ATSM 2014 09 Aqua tempo power series tropical air cooled scroll chiller 50Hz 59 45...
Page 64: ...Aqua tempo power series tropical air cooled scroll chiller 50Hz MCAC ATSM 2014 09 62 40...
Page 65: ...MCAC ATSM 2014 09 Aqua tempo power series tropical air cooled scroll chiller 50Hz 63...
Page 73: ...MCAC ATSM 2014 09 Aqua tempo power series tropical air cooled scroll chiller 50Hz 71 57...