Service Manual
, 2016-12
32
/
47
multiple wifi environment, the user
can select which wifi to connect
through the App.
1
Compressor
compulsory
running Mode
During manufacturing and ex-factory
testing, this mode will be used to test
the refrigerating capacity. For after
sales service, this mode is used for
compressor activate problem check.
Using for ex-factory
and after sales
service test.
Can be
canceled
2
Deforest
heater
compulsory
running Mode
During manufacturing and ex-factory
testing, this mode will be used to test
the deforest heater capacity. For
after sales service, this mode is used
for deforest heater activate problem
check.
Using for ex-factory
and after sales
service test.
Can not be
canceled
9.1Self-diagnosis
1)Enter: With 5 seconds after power on, if there is no sensor failure and the freezer sensor
temperature
≥
0
℃
, it will enter into self-diagnosis
2)Exit: after
20min it will exit the Self-diagnosis immediately to enter normal mode
3)Process of Self-diagnosis
1. Switch on the defrosting heater for 5 seconds, then switch off for 5 seconds
2. Switch on the fan motor for 5 seconds, then switch off for 5 seconds
3. turn on the fan motor and compressor at same time
4.it will exit the self-diagnosis after 20 minutes.
Summary of Contents for 22031010000841
Page 5: ...Service Manual 2016 12 5 47 1 Safety Warning Code 1 1Warning for operation safety...
Page 6: ...Service Manual 2016 12 6 47...
Page 7: ...Service Manual 2016 12 7 47...
Page 8: ...Service Manual 2016 12 8 47 1 2Safety instruction for refrigerant...
Page 37: ...Service Manual 2016 12 37 47 11 Troubleshooting Method 11 1 No refrigeration...
Page 38: ...Service Manual 2016 12 38 47 11 2 Compressor failure...
Page 39: ...Service Manual 2016 12 39 47 11 3 Defrosting is not working...