TECHNICAL SPECIFICATIONS
Model
UPS-OLEBPR-2
UPS-OLEBPR-1
Configuration
AC
Input
Voltage
100~125Vac
DC
Output
Voltage
36Vdc
72Vdc
Amperage
60A
Physical
Dimensions (L x W x H)
16.9 x 17 x 3.5in.
(430 x 433 x 88mm)
23.6 x 17 x 3.5in.
(600 x 433 x 88mm)
Net
Weight
50.6lbs(23.0Kg)
96.8lbs(44.0Kg)
Battery
Specifications
Qty 6
(2 x Banks of 3 Batteries)
Qty 12
(2 x Banks of 6 Batteries)
Recharge Time (Typically)
5 hours for 0-100% Capacity; 4 hours for 0-90% Capacity
Interface
PP45
Sealed,
Maintenance
Free
Yes
Hot-Swappable
Yes
Built-in
Charger
Yes
Environment
Operating
Temperature
32
℉
to 104
℉
(0
℃
to 40
℃
)
Operating Relative Humidity
0 to 90% Non-Condensing
Safety
Conformance
Approvals
UL
RoHS
RoHS
Compliant
TROUBLESHOOTING
Problem
Possible Cause
Solution
Warning
BAT Disconnected
Missing battery power.
Check battery connector and battery breaker.
Battery Failure
The UPS has detected a bad battery.
1. Check battery connector and battery breaker.
2. Contact technical support at 1-800-266-7225
for more information about Middle Atlantic
Product’s Battery Replacement Program.
Replace Battery
Battery will soon need to be replaced due to
insufficient runtime.
Contact technical support at 1-800-266-7225 for
more information about Middle Atlantic Product’s
Battery Replacement Program.
Fault
Overcharge Battery
is
overcharged.
1. Remove battery connector and check
charger voltage.
2. Contact technical support at 1-800-266-7225
for repair information.
Charger Failure
Charger has failed.