16
4.2.4 Keyboard lock
To avoid mis-operation, please lock the controller after parameter setting.
At the main interface, press
for 5 seconds, the keyboard will be locked.
When the keyboard is locked, press
for 5 seconds, the keyboard will be
unlocked.
NOTES: When the unit is in alarming state, the key lock can be removed automaticly.
TEMP
IN
C
TEMP
OUT
MODE
SET
Hold on
Locked
TEMP
IN
C
TEMP
OUT
MODE
SET
MODE
SET
4.2.5 Malfunction display
There will be malfunction code showing on the controller screen when relative
malfunction occurs.
You can refer to the malfunction table to find out the failure cause and solution.
For example
Water inlet temp. Sensor failure
4. USAGE AND OPERATION
27
27
27
Meaning
Heating inlet target temp.
Adjustable
Adjustable
Adjustable
4.3 Parameter table
Cooling inlet target temp.
Auto inlet target temp.
Remark
Default