MC • Karl Dungs
, Inc.
•
Vent Line A
dapter f
or DMV • Edition 2016.02 • P/N 261432
Installing the Vent Line Adapter
Recommended Preparation
• The power and main gas supply must be shut off before
starting the installation.
• Read these installation instructions carefully.
• Examine the inside of the valve, vent line adapter and
flanges. All piping must be clean and free of dirt.
Recommended Procedure to mount the Vent Line
Adapter (VLA)
1. Using a 4 mm Allen driver, remove the side plate (located
on either side of the valve) on which the VLA will be in
-
stalled.
2. Insert the new o-rings supplied with the VLA in the ap
-
propriate grooves locate on the back side of the VLA.
3. Mount the VLA to the valve so that the 1” NPT port is ori
-
entated towards the top of the valve.
4. Secure the VLA to the DMV with the 4 mm screws included
with the VLA. Tighten in a criss cross pattern while torquing
each screw to 45 lb-in.
5. After installation is completed, use a gas leak detection
solution to leak test the vent line adapter to confirm that
no leakage occurs. The presence of bubbles indicates a
leak.
Side plate to
be removed
O-ring grooves
1” NPT
connection