Microtrol Black Pear TXIO Installation And User Manual Download Page 2

Summary of Contents for Black Pear TXIO

Page 1: ...TXIO Third Party Equipment Interface for Toshiba TCC Link Installation and User Guide www microtrol co uk ...

Page 2: ......

Page 3: ...3 1 Power Supply 4 3 2 HVAC Communications Network TCC LINK 4 3 3 Relay Output 4 3 4 Error Input 4 3 5 Thermistor Input 4 4 Configuration 5 4 1 S1 Bitswitch Function 5 4 2 S2 Link Function 6 4 3 LED Functions 7 Appendix A Physical Dimensions 8 Appendix B Document Revision History 9 ...

Page 4: ...ion regulations Ensure that installation work is done correctly using the information contained in this manual Make all connections securely so that any outside forces acting on the cables are not applied to the terminals Never modify or repair the Black Pear by yourself Any attempt to do so will void the warranty To dispose of this product consult your dealer ...

Page 5: ...r parameters On Off is provided as a relay output rated at 230v 1A A digital input provides an error monitoring facility with the error being reported as a C12 The polarity of the input is selectable Return air may be monitored by connecting a 10K301 thermistor 3 Connection Details All electrical work should be carried out by a competent person and wiring must be in accordance with the national el...

Page 6: ... are non polarized Do not connect to the remote controller network 3 3 Relay Output The relay output is rated at 230V 1A Normally open and normally closed terminals are provided 3 4 Error Input This input accepts a volt free contact The polarity of the active state is selectable via a shorting link See section 4 2 3 5 Thermistor Input Connecting a 10K301 thermistor to this input allows a temperatu...

Page 7: ...nnected across the TCC Link lines Off No terminating resistor Note Only one terminating resistor should be enabled per network S1 2 On Auto Restart retain the I O state as it was at power down Off Start in the OFF condition Fig 2 LEDs and Config Switches S1 Bitswitch S2 Link ...

Page 8: ...OFF 3 4 5 6 7 8 59 ON OFF 3 4 5 6 7 8 8 ON OFF 3 4 5 6 7 8 21 ON OFF 3 4 5 6 7 8 34 ON OFF 3 4 5 6 7 8 47 ON OFF 3 4 5 6 7 8 60 ON OFF 3 4 5 6 7 8 9 ON OFF 3 4 5 6 7 8 22 ON OFF 3 4 5 6 7 8 35 ON OFF 3 4 5 6 7 8 48 ON OFF 3 4 5 6 7 8 61 ON OFF 3 4 5 6 7 8 10 ON OFF 3 4 5 6 7 8 23 ON OFF 3 4 5 6 7 8 36 ON OFF 3 4 5 6 7 8 49 ON OFF 3 4 5 6 7 8 62 ON OFF 3 4 5 6 7 8 11 ON OFF 3 4 5 6 7 8 24 ON OFF 3 ...

Page 9: ...7 4 3 LED Functions LED 3 Blue Power Flashing In Error LED 2 Red TCC Link Comms Flashes for each message LED 1 Amber Output State On Active ...

Page 10: ...8 Appendix A Physical Dimensions Power Supply USB 107mm 33mm 110mm Fig 3 Dimensions ...

Page 11: ...pendix B Document Revision History Date Document Ver Firmware Ver By Comments 01 07 2017 v1 00 v1 10 mcb First version converted from preliminary instructions 05 07 2017 v1 01 v1 10 mcb Converted to booklet ...

Page 12: ...Microtrol Ltd 16 Elgar Business Centre Moseley Road Hallow Worcester WR2 6NJ UK Tel 44 0 1905 641910 Email sales microtrol co uk ...

Reviews: