12. HIDDEN SYSTEM PARAMETERS
USED ONLY BY SERVICE SPECIALIST!
WRONG SETTINGS MAY LEAD TO THE INCORRECT FUNCTION OF THE DEVICE!
Hidden system parameters are “visible’’ only until the next shut down.
To access hidden system parameters, it’s needed to feed the power supply while holding
and pressing the
UP
button. In this case, in the list of system parameters, after
End,
the
following ones appear:
Name
Description
Values
Fr 1
Filter coefficient for Channel 1
0 - 128 units
A lower value corresponds to a
“heavier” filter of the input variable
tJ 1
Waiting time before a filter jump for
Channel 1
0 - 128 seconds
JP 1
Filter rebound threshold of Channel 1
0 .. 255 units of input
When changing the input variable to a
value greater than the preset and
maintaining the new state for a time
greater than
tJ 1
, the filter bounces
and takes the new value directly.
Fr 2
Filter coefficient for Channel 2
0 - 128 units
A lower value corresponds to a
“heavier” filter of the input variable
tJ 2
Waiting time before a filter jump for
Channel 2 when changing the input
variable with a value greater than
JP 2
.
0 - 128 seconds
JP 2
Filter rebound threshold of Channel 2
0 .. 255 units of input
When changing the input variable
to a value greater than the preset and
maintaining the new state for a time
greater than
tJ 2
, the filter bounces
and takes the new value directly.