mipan PN
Numeric Panel-Mount LED Display with Profinet IO RT Interface
Page 7
microSYST Systemelectronic GmbH, Am Gewerbepark 11, 92670 Windischeschenbach
+49 9681 91960-0,
+49 9681 91960-10, [email protected], www.microsyst.de
5.2 Configuration of the Profinet Controller
The Profinet controller must be configured properly in order to communicate
with the Profinet device.
The following descriptions refer to the "HW Config" tool from Siemens and
are intended to represent the principle. This works of course with the tools of
other manufacturers.
First, the GSDML file
(“GSDML-V2.2-microSYST-01CF-MifacePNIO-....xml“)
has to be a
dded to the „device catalogue“ of the configuration tool (menu
item „Options/Install GSD File...“). Then, the device is shown in the cata-
logue view as follows:
Now you can choose between 3 different „Device Access Points“:
- DAP1 (no PDEV),
if your Profinet controller does not know a „physical device“
(usually only with older Profinet controllers)
- DAP2 (standard, no MRP),
if the MRP ability of the device shall not be activated.
-
DAP3 (standard)
,
if the MRP ability of the device shall be activated.
„Drag“ the needed „DAP“ to your Profinet system: