Manual Teach-in
Set room controller to pairing mode.
Check the user guide of the
room controller.
Teach-in t
hrough Re
Man/
ReCom: Pl
ease, cont
act
Micropelt
/EH4 Gmb
H.
Room controller
EnOcean EEP A5-20-01
Ambient
temperature sensor
Button
LED
(below cover)
Quick Start –
self-powered iTRV
MVA-003
Pairing-mode
Press the push button twice. You may have to repeat this step.
Installation and reference run
After installing, press the push button once; the iTRV adjusts
the min and max positions. Then enters normal operation.
During the following
10 minutes the iTRV works
at a 10-second intervals.
Non-installed iTRVs return
into mounting position.
LED flash pattern
1 x flash = Successful pairing
6 x flash = Pairing failed
Additional things to know
•
Connection nut M30 x 1.5; adapters are available
for many other valve types
•
Valve should be working freely
•
EnOcean protocol A5-20-01
•
Every 10 minutes, the iTRV connects to the room
controller, requesting an update to the valve position
or the set temperature. The iTRV then moves the valve
to the specified position.
•
Summer mode: Radio communication interval increased
from 10 minutes to 8 hours
•
To remove the iTRV, press the push button twice and
wait until the motor stops. Then loosen the coupling nut.