U1000MKII User Manual
Micronics
Page 42
Issue 3.1 July 19
4.4.7
Change Primary Address Function
COMMAND:
SEND_UD
–
SET PRIMARY ADDRESS
DESCRIPTION:
The primary address of the slave is set to a default value at power up.
The master uses this command to assign a new unique primary
address to the slave if required.
DIRECTION:
MASTER TO SLAVE
FRAME TYPE:
LONG FRAME
PRIMARY ADDRESSING
SECONDARY ADDRESSING
NAME
CODE
NAME
CODE
START
0x68
START
0x68
LENGTH
0x06
LENGTH
0x0E
LENGTH
0x06
LENGTH
0x0E
START
0x68
START
0x68
(C - FIELD)
SEND_UD
0x73
(C - FIELD)
SEND_UD
0x73
(A - FIELD)
SLAVE PRIMARY ADDRESS
0xXX
(A - FIELD)
USE SECONDARY
ADDRESSING
0xFD
(CI
–
FIELD)
0x51
(CI
–
FIELD)
0x51
DIF: 8 BIT INTEGER
0x01
M-Bus IIN (BYTE 1)
0xXX
VIF: SET PRIMARY ADDRESS
0x7A
M-Bus IIN (BYTE 2)
0xXX
NEW PRIMARY ADDRESS
VALUE
0xXX
M-Bus IIN (BYTE 3)
0xXX
CHECKSUM
0xXX
M-Bus IIN (BYTE 4)
0xXX
STOP
0x16
MANF. ID (BYTE 1)
0xCD
MANF. ID (BYTE 2)
0x54
VERSION NUMBER
0x01
DEVICE TYPE ID
0x04
DIF: 8 BIT INTEGER
0x01
VIF: SET PRIMARY ADDRESS
0x7A
NEW PRIMARY ADDRESS
VALUE
0xXX
CHECKSUM
0xXX
STOP
0x16
MASTER TO SLAVE: SEND_NKE
SLAVE TO MASTER: ACK
MASTER TO SLAVE: SEND_UD
–
SET PRIMARY ADDRESS
SLAVE TO MASTER: ACK