Microlectra Dinel DLS-27 Series Instruction Manual Download Page 17

17

© 

Dinel      DLS–27

   

12. S

afety

ProtectionS

comPatibility

 

and

 

exPloSion

 

Proof

Level sensor DLS–27 is equipped with protection against electric shock on electrode, reverse polar-

ity, output current overload, short circuit and short time over voltages.

Electromagnetic  compatibility  is  provided  by  conformity  with  standards  EN  55022 / B,  EN  61326-1,

 

EN 61000-4-2, -3 ,-4, -5 and -6. 

Explosion  proof  (DLS–27Xi,  XiM  and  Xd)  is  provided  by  conformity  with  standards  EN  60079-0,

 

EN 60079-11, EN 60079-26 and is examined by FTZÚ – AO210 Ostrava – Radvanice, certificate No. 

FTZÚ 02 ATEX 0234X. 
Explosion proof (DLS–27Xd) is provided by conformity with standards EN 60079-0, EN 60079-31 and 

 

is examined by FTZÚ – AO210 Ostrava – Radvanice, certificate No. FTZÚ 10 ATEX 0092X.

Supplied electrical equipment matches the requirements of valid European directives for safety and 

electromagnetic compatibility. The declaration of Conformity for the above mentioned product was 

issued.

Special conditions for safe use of variants DLS-27Xi (Xit, XiM, XiMt)

If the apparatus is used as device of Group II and with using of an approved power supply device, 

which output parameters comply with required input parameters, it is necessary to have an galvanic 

separation or in case of apparatus without galvanic separation (Zener barriers) it is necessary to 

provide equipotential equalizing between sensor and barrier earthing point.
If the apparatus is used in coal mine as device of Group I and with using of an approved power 

supply device, which output parameters comply with required input parameters it is necessary to 

have an galvanic separation.

When used in zone 0 the present explosive atmosphere of air mixture and gases, vapours of mists 

must be comply with: 20°C ≤ T

amb

 ≤ 60°C, 0.8 bar ≤ p ≤ 1.1 bar.

Design DLS–27Xi can be used in zone 0 or zone 20. With design DLS–27XiT can be used in zone 

0 and zone 20 only electrode part head with electronics can be used only in zone 1 or zone 21.

Ambient temperature: T

amb

 = -20°C to +75°C

Temperature of measured medium according to design variant see chapter “Specification”.

For design DLS–27XiMT it is necessary to observe that temperature of any surface of apparatus, 

when coal dust can from a layer, do not exceed 150°C.

Special conditions for safe use of variant DLS-27Xd

Ambient temperature: T

amb

 = -20°C to +70°C

The sensor DLS-27Xd is designed with permanent cable. The cable must be terminated in connection 

box with degree of protection IP 6X. 
The end of the sensor must be protected against direct daylight.
Maximum effective value of AC or DC voltage that can be applied to the terminals of device, which 

are not intrinsically safe, without breaking the type of protection is U

m

 = 253 V.

Summary of Contents for Dinel DLS-27 Series

Page 1: ...at a safe place The manufacturer reserves the right to implement changes without prior notice INSTRUCTION MANUAL pr myslov elektronika Capacitive level sensors DLS 27 www microlectra nl Microlectra bv...

Page 2: ......

Page 3: ...ion 12 7 Sensor setting 13 8 Status signalization 14 9 Accessories 15 10 Order code 16 11 Correct specification examples 16 12 Safety protections compatibility and explosion proof 17 13 Use manipulati...

Page 4: ...during the transport did not occurred the damage of the packaging or the equipment The device apparently damaged during transport do not use and contact the manufacturer to resolve the situation If t...

Page 5: ...slant from the side Electrode length from 0 1m to 3m DLS 27_ 31 Fully coated rod electrode for sensing aggressive electrically conductive liquids water solutions of chemicals vertical mounting Electro...

Page 6: ...Dinel 6 3 Dimensional drawings DLS 27_ 10 DLS 27_ 11 DLS 27_ 20 DLS 27_ 21 22 DLS 27_ 30 DLS 27_ 31 DLS 27_ 40 High temperatures variants Tri clamp process coupling Thead Type of threads G 3 4 M27x2 M...

Page 7: ...cally mounted sensors 20 E 40 b 50 E 10 c 40 E 40 d 20 E 20 k E 3 1 E 10 1 a 20 E 40 b 50 E 10 c 40 E 40 d 20 E 20 k E 3 4 s E 3 1 E 10 1 a 20 E 40 b 50 E 10 c 40 E 40 d 20 E 20 k E Electrode length i...

Page 8: ...unting In the case of side wall mount ing it is necessary to avoid long fit ting tubes where could the rests of sensed media cumulate see the right figure We recommend to mount the sensor so that the...

Page 9: ...hich is permanently dipped into the medium e g conductive probe CNP 18 or can be use the auxiliary plate electrode PDE 27 where the first part has thread for install of the sensor and the second part...

Page 10: ...pe it is nec essary to provide the minimum distance of the inner walls from the electrode at 5 mm In some cases sticky fluids low permittiv ity liquids it is better to mount the sensor to pipe bend Fo...

Page 11: ...is possible to use it for non conductive fluids with up to 2 of water plant oils liquid propane etc The sensor with electrode longer than 300 mm is recom mended to mount in vertical position only Sen...

Page 12: ...ically conductive liquids are sensed just by touch of the end of electrode To react to non conductive liquid or solid material it is neces sary 5 20 dip into a medium dependently on the permittivity o...

Page 13: ...s possible to achieve resistance against sediments LED Hysteresis Cable outlet or connector Fig 17 Top view of level sensor Sensitivity Electrical connection must be done in de energized state For swi...

Page 14: ...reverse direction turning makes it lower The lower the hysteresis is the higher sensitivity is possible to obtain but the resistance against various disturbances get worse For usual applications is op...

Page 15: ...__ _ PC _ DLS 27Xd __ D PC _ CLOSED Shine DLS 27Xi __ _ RC _ HIGHER CURRENT DLS 27N_ __ _ NC _ DLS 27Xd __ D NC _ DLS 27N_ __ _ PC _ DLS 27Xd __ D PC _ OPEN Dark DLS 27Xi __ _ RC _ LOWER CURRENT 9 Acc...

Page 16: ...n mines Process connection G Pipe thread G3 4 M27 Metric thread M27x2 M30 Metric thread M30x1 5 Cl Tri clamp coupling 10 Order code 11 Correct specification examples DLS 27N 10 B NO M27 E100 cable 5m...

Page 17: ...without galvanic separation Zener barriers it is necessary to provide equipotential equalizing between sensor and barrier earthing point If the apparatus is used in coal mine as device of Group I and...

Page 18: ...z dinel dinel cz Czech Republic I 15 mA i P 45 mW i t 20 60 C zone 0 a L 10 uH i t 20 75 C a II 1 D Ex ia IIIC Da T 76 C IP67 BN BU U 0V II 1 2 G Ex ia IIB T6 Ga Gb U 12 V i FTZ 02 ATEX 0234X C 15 nF...

Page 19: ...ltage U 7 27 V Current supply I 3 7mA Switching current Iomax 150 mA Ambient temperature range ta 20 60 C Number of certificate of intrinsically safety FTZ 10 ATEX 0092X Compliance mark Number of auth...

Page 20: ...V AC Coupling capacity Electric strength 47 nF 250 V AC Protection class IP67 Cable version with cable outlets PVC 3 x 0 5 mm2 or 2x0 75 mm2 Weight excl electrode cable 2 m DLS 27_ DLS 27_T Approx 0 4...

Page 21: ...XiT XiMT Working areas EN 60079 10 14 and EN 50281 1 2 DLS 27N Performance for non explosive areas DLS 27NT High temperature performance for non explosive areas DLS 27Xd Performance for flammable dus...

Page 22: ...0 40 C 200 C 40 C 200 C 20 C 80 C 3 MPa 2 MPa 0 5 MPa 0 3 MPa 0 1 MPa DLS 27NT 20 30 40 C 300 C 40 C 200 C 20 C 80 C 3 MPa 2 MPa 0 5 MPa 0 3 MPa 0 1 MPa DLS 27Xd 20 70 C 20 70 C 20 70 C 3 MPa 2 MPa DL...

Page 23: ...the source and connect it again The sensor is evidently set so that it has too large hysteresis and the change of the capacity after deactivation is insufficient for exceeding the area of hysteresis...

Page 24: ...industrial electronics Microlectra bv Augustapolder 12 2992 SR Barendrecht The Netherlands www microlectra nl info microlectra nl...

Reviews: