2.4 - CLOCK AND CALENDAR 

 

The unit features a built in clock calendar with Years, Months, Days, Hours, Minutes, Seconds, Tenths 
of seconds and Hundredths of seconds. 

 

2.4.1 - Clock synchronization. 

 

The clock can be synchronized via the serial communication interface. 
The following synchronization periods can be set: 5, 10, 15, 30, 60 minutes. 
Synchronization can also be disabled, in which case the relay ignores the serial broadcast signal. 
In case synchronization is enabled, the unit expects to receive a sync signal at the beginning of every 
hour and once every T

syn

 minutes. When a sync signal is received, the clock is automatically set to 

the nearest expected synchronization time.  
For example: if T

syn

 is 10min and a sync signal is received at 20:03:10 January the 10

th

, 98, then the 

clock is set to 20:00:00 January the 10

th

, 1998.  

On the other hand, if the same sync signal were received at 20:06:34, the clock would be set to 
20:10:00, January the 10

th

 98. 

Note that if a sync signal is received exactly in the middle of a T

syn

 period, the clock is set to the 

previous expected synchronization time. 

 

2.4.2 - Date and time setting. 

 

When the PROG/SETTINGS menu is entered, the current date is displayed with one of the groups of 
digits (YY, MMM or DD) blinking.  
The DOWN key operates as a cursor. It moves through the groups of digits in the sequence YY => 
MMM => DD => YY => … 
The UP key allows the user to modify the currently blinking group of digits. 
If the ENTER button is pressed the currently displayed date is set.  
Pressing the SELECT button the current time is displayed which can be modified using the same 
procedure as for the date. 
If synchronization is enabled and the date (or time) is modified, the clock is stopped until a sync 
signal is received via the serial port. This allows the user to manually set many units and have them 
to start their clocks in a synchronized fashion. 
If synchronization is disabled the clock is never stopped. 
Note that the setting of a new time always clears 10ths and 100ths of sec. 

 

2.4.3 - Time resolution. 

 

The clock has a 10ms resolution. This means that any event can be time-stamped with a 10ms 
accuracy, although the information concerning 10ths and 100ths of sec. can be accessed only via the 
serial communication interface. 

 

2.4.4 - Operation during power off. 

 

The unit has an on board Real Time Clock which maintains time information for at least 1 hour in 
case of power supply failure. 

 

2.4.5 - Time tolerance. 

 

During power on, time tolerance depends on the on board crystal (+/-50ppm typ, +/-100ppm max. 
over full temperature range). 
During power off, time tolerance depends on the RTC’s oscillator (+65 /–270 ppm max over full 
temperature range). 

 

Summary of Contents for MM30-D

Page 1: ...MM30 D Doc N MO 0037 ING Rev 4 Date 24 02 2003 Copyright 2010 Microener Pag 1 of 36 MICROPROCESSOR MOTOR PROTECTION RELAY WITH DIRECTIONAL EARTH FAULT ELEMENT TYPE MM30 D OPERATION MANUAL...

Page 2: ...resolution__________________________________________________________________________ 13 2 4 4 Operation during power off_________________________________________________________________ 13 2 4 5 Time...

Page 3: ...must be compatible with their declared performance 1 6 PROTECTION EARTHING When earthing is required carefully check its effectiveness 1 7 SETTING AND CALIBRATION Carefully check the proper setting of...

Page 4: ...alibrations and components should not be altered or replaced For repair please ask the Manufacturer or its authorised Dealers Misapplication of the above warnings and instruction relieves the Manufact...

Page 5: ...ary of the input Current Transformers and refers all its measurements to that value To make the relay properly working with any C T when programming the relay settings we have to input the value of th...

Page 6: ...are correctly measured in any case two directly 2 2 2 3 Earth Fault Current and Voltage Inputs The real time measurement of the r m s Earth Fault Current is displayed as percent of the rated current...

Page 7: ...omputed current Ip preheating current Ib continuously admissible current 1 1 3 Im step 0 01Im Im motor rated current 0 1 1 5 In step 0 1In Steady motor cooling down time constant to 1 10 tm step 1tm T...

Page 8: ...nbalance also controls another inverse time element Minimum Negative Sequence current operation level Is 0 1 0 8 Im step 0 1lm lf ls DIS the function is disactivated Time current curve tIs 1 8 s step...

Page 9: ...MM30 D Doc N MO 0037 ING Rev 4 Date 24 02 2003 Copyright 2010 Microener Pag 9 of 36...

Page 10: ...energized for the time tI tBO After this delay the relay it is anyhow reset tBO 0 05 0 5 s step 0 05s 2 2 3 7 F64 Earth Fault protection Minimum Pick up Zero Sequence Residual Current level O 0 02 2 O...

Page 11: ...the inhibition is permanent until the RESET key is operated 2 2 3 9 Starting Sequence Control During start up of the motor the unit can control an output relay used to operate the switch over of two...

Page 12: ...tep 1A Motor rated current lm 0 1 1 5 In step 0 01In Motor starting current lst 0 5 9 9 Im step0 1 Im Starting time tst 1 120 s step 1s Transition current level ITr 0 11 Ist step 0 1 Ist Transition ti...

Page 13: ...Io cos o o Fig 1 Fig 2 The relay measurement is 3Io x cos o o Io The relay trips when Io O fig 2 i e when the component of the input current in the measuring direction of the relay exceeds the set tri...

Page 14: ...displayed with one of the groups of digits YY MMM or DD blinking The DOWN key operates as a cursor It moves through the groups of digits in the sequence YY MMM DD YY The UP key allows the user to mod...

Page 15: ...ter scanning by the key SELECT Parameter modification by the key Set validation by the key ENTER Scanning of the menus by the key MODE SELECT ENTER Enabled only if input current is zero ENTER RESET MO...

Page 16: ...LED O Flashing when earth fault current exceeds the set level O Illuminated on trip after tO time delay h Yellow LED ROTOR STALL Illuminated on trip of the Locked Rotor element I ILR and or on activat...

Page 17: ...orts see diagram herebelow The module REX 8 includes eight RA RB RC RD RE RF RH RG user programmable plus one R Diag diagnostic output relays The master module MM30 DX can control altogether up to six...

Page 18: ...ption can be connected via a cable bus or with proper adapters a fiber optic bus for interfacing with a Personal Computer type IBM or compatible All the operations which can be performed locally for e...

Page 19: ...robe This function is enabled by programming the variable RTD ON see 12 1 If the function is enabled the input RTD is activated when the resistance connected to the terminals 1 14 exceeds the limits 5...

Page 20: ...in the memory SET DISP Reading of the settings and of the configuration of the output relays as programmed PROG Access to the programming of the settings and of relay configuration TEST PROG Access t...

Page 21: ...e degree 0 999 Uo xxxxxV RMS Voltage displayed as primary volts 0 65000 o xxx Phase displacement h xxxxx Operation hours 0 65000 If no keys is operated in 60 sec the display comes back to the default...

Page 22: ...rrent Is mxxx Negative sequence component of current T Tnxxx Motor heating UoxxxxxV Zero sequence secondary voltage oxxxxx Io Uo phase displacement angle in degrees 10 4 TRIP NUM Counters of the numbe...

Page 23: ...he key SELECT now scrolls the available parameters By the key the displayed values can be modified to speed up parameter s variation press the key SELECT while or are pressed Press key ENTER RESET to...

Page 24: ...during run 1 25 1 s Is 0 3Im Trip level of inverse time current unbalance protection element Dis 0 1 0 8 0 1 Im tIs 4s Trip time delay of inverse time current unbalance protection when I2 Im 1 8 1 s...

Page 25: ...1 R2 R3 R4 RA RB RL StNo 1 Start No limitation tripping operates relay R1 R2 R3 R4 RA RB RL ILR 1 Locked Rotor tripping operates relay R1 R2 R3 R4 RA RB RL tI2 1 Time delayed unbalance tripping operat...

Page 26: ...est It is generally recommended that this test be run only in a bench test environment or after all dangerous output connections are removed 14 MAINTENANCE No maintenance is required Periodically a fu...

Page 27: ...1MHz Electrical fast transient burst IEC61000 4 4 level 3 2kV 5kHz HF disturbance test with damped oscillatory wave 1MHz burst test IEC60255 22 1 class 3 400pps 2 5kV m c 1kV d m Oscillatory waves Ri...

Page 28: ...MM30 D Doc N MO 0037 ING Rev 4 Date 24 02 2003 Copyright 2010 Microener Pag 28 of 36 16 CONNECTION DIAGRAM SCE1423 Rev 2 Standard Output 16 1 CONNECTION DIAGRAM SCE1499 Rev 0 Double Output...

Page 29: ...MM30 D Doc N MO 0037 ING Rev 4 Date 24 02 2003 Copyright 2010 Microener Pag 29 of 36 17 WIRING THE SERIAL COMMUNICATION BUS SCE1309 Rev 0 18 CHANGE PHASE CURRENT RATED INPUT 1 OR 5A...

Page 30: ...MM30 D Doc N MO 0037 ING Rev 4 Date 24 02 2003 Copyright 2010 Microener Pag 30 of 36 19 THERMAL IMAGE CURVES TU0249 Rev 1...

Page 31: ...MM30 D Doc N MO 0037 ING Rev 4 Date 24 02 2003 Copyright 2010 Microener Pag 31 of 36 20 INVERSE TIME UNBALANCE PROTECTION ELEMENT TU0248 Rev 1...

Page 32: ...osition of the screws driver mark Draw out the PCB by pulling on the handle 21 2 Plug in Rotate clockwise the screws and in the horizontal position of the screws driver mark Slide in the card on the r...

Page 33: ...MM30 D Doc N MO 0037 ING Rev 4 Date 24 02 2003 Copyright 2010 Microener Pag 33 of 36 22 OVERALL DIMENSIONS MOUNTING...

Page 34: ...MM30 D Doc N MO 0037 ING Rev 4 Date 24 02 2003 Copyright 2010 Microener Pag 34 of 36 23 KEYBOARD OPERATIONAL DIAGRAM...

Page 35: ...hermal time constant 3 1 10 Ta n Prealarm motor heating level 90 50 110 Ts n Motor restart heating level 100 40 100 Ib Rated maximum continuous motor overload 1 05 Im 1 1 3 StNo Max No of startings al...

Page 36: ...Ta ITr Starting switch over tripping ITr StNo 1 Start No limitation tripping StNo ILR 1 Locked Rotor tripping ILR tI2 1 Time delayed unbalance tripping tI2 I No load running tripping I I Instantaneou...

Reviews: