MC3V-X/10-4
Doc. N°
MO-0355-ING
Microe
ner
- Copyright 20
11
FW
940.09.01.x
Date
06
.0
1
.20
11
Rev.
4
Pag.
23
of
32
11.5.4 - Function
(Functions)
-
“ Function “,
-
1
st
function,
-
to scroll available Functions,
-
to Read/Write setting of the selected function,
-
FuncEnab
-
TripLev
-
to select the different definable fields
-
Options
-
Timers
-
to access the selected field and read the actual
setting of the relevant variable
-
to modify the actual setting;
-
to set the new value.
-
to validate.
Set Done!
Display
Function
Type
Variable
Default
Setting
Unit
Description
Setting Range
Step
Password
=
0000-9999
1111
-
Password for programming enable (see § Password)
FuncEnab
→
Enable
Enable of the protection function
Enable/Disable
-
BI
Disable
Operation controlled by Blocking Digital Input
Enable/Disable
-
Options
→
Trg
Enable
Function operation triggers the oscillographic wave
form capture
Enable/Disable
-
TripLev
→
V>
1.10
Vn
Trip level of overvoltage protection
0.50 – 1.50
0.01
V>
(1F59)
Timers
→
tV>
1.00
s
Trip time delay
0.05 – 60.00
0.01
FuncEnab
→
Enable
Enable of the protection function
Enable/Disable
-
BI
Disable
Operation controlled by Blocking Digital Input
Enable/Disable
-
Options
→
Trg
Enable
Function operation triggers the oscillographic wave
form capture
Enable/Disable
-
TripLev
→
V>>
1.30
Vn
Trip level of overvoltage protection
0.50 – 1.50
0.01
V>>
(2F59)
Timers
→
tV>>
0.30
s
Trip time delay
0.05 – 60.00
0.01
FuncEnab
→
Enable
Enable of the protection function
Enable/Disable
-
BI
Disable
Operation controlled by Blocking Digital Input
Enable/Disable
-
Options
→
Trg
Enable
Function operation triggers the oscillographic wave
form capture
Enable/Disable
-
TripLev
→
V<
0.90
Vn
Trip level of undervoltage protection
0.20 – 1.20
0.01
V<
(1F27)
Timers
→
tV<
1.00
s
Trip time delay
0.05 – 60.00
0.01
FuncEnab
→
Enable
Enable of the protection function
Enable/Disable
-
BI
Disable
Operation controlled by Blocking Digital Input
Enable/Disable
-
Options
→
Trg
Disable
Function operation triggers the oscillographic wave
form capture
Enable/Disable
-
TripLev
→
V<<
0.70
Vn
Trip level of undervoltage protection
0.20 – 1.20
0.01
V<<
(1F27)
Timers
→
tV<<
0.30
s
Trip time delay
0.05 – 60.00
0.01
FuncEnab
→
Enable
Enable of the protection function
Enable/Disable
-
BI
Disable
Operation controlled by Blocking Digital Input
Enable/Disable
-
Options
→
Trg
Enable
Function operation triggers the oscillographic wave
form capture
Enable/Disable
-
TripLev
→
f>
50.50
Hz
Trip level of overfrequency protection
40 – 70
0.01
f>
(F81)
Timers
→
tf>
1.00
s
Trip time delay
0.05 – 60.00
0.01
FuncEnab
→
Enable
Enable of the protection function
Enable/Disable
-
BI
Disable
Operation controlled by Blocking Digital Input
Enable/Disable
-
Options
→
Trg
Enable
Function operation triggers the oscillographic wave
form capture
Enable/Disable
-
TripLev
→
f<
40.50
Hz
Trip level of underfrequency protection
40 – 70
0.01
f<
(F81)
Timers
→
tf<
1.00
s
Trip time delay
0.05 – 60.00
0.01