![MICROELETTRICA MC30-BC Operation Manual Download Page 27](http://html1.mh-extra.com/html/microelettrica/mc30-bc/mc30-bc_operation-manual_1786336027.webp)
MC30-BC
Doc. N°
MO-0365-ING
Copyright 2008
FW 980.09.01.X
Date
15.06.2022
Rev.
1
Pag.
27
of
37
12. Menu and Variables
12.1 - Real Time Measurements
Automatic scrolling display of the Real Time Measurements is the Default operation.
Scrolling can be stopped at any of the measurements and restarted by pressing the Reset button
.
When stopped on one variable, a mark
appears aside the measurement.
The different measurements can be manually scrolled by the
buttons.
Display
Description
I
= 0
–
65535
%In Largest of the 3 phase-currents (% of rated current)
IA
= 0
–
65535
A
RMS value of Phase A current
IB
= 0
–
65535
A
RMS value of Phase B current
IC
= 0
–
65535
A
RMS value of Phase C current
Io
= 0.0
–
6553.5
A
RMS value of Zero Sequence Current (RMS Primary Amps)
I1
= 0
–
65535
%
Direct sequence
I2
= 0
–
65535
%
Inverse sequence
Tem
= 0 - 65535
%T
Actual temperature rise
SR
= 0
–
65535
%
Inverse sequence / Direct sequence
12.2 - Meas (Instantaneous Measurements)
Real time measurements can be frozen at any moment selecting the menu “Instant Measure”
:
“
R
eal
T
ime
M
eas”
“Measure”
“1
st
Measurement
other measurements
to go back to “Measure”
Display
Description
I
= 0
–
65535
%In Largest of the 3 phase-currents (% of rated current)
IA
= 0
–
65535
A
RMS value of Phase A current
IB
= 0
–
65535
A
RMS value of Phase B current
IC
= 0
–
65535
A
RMS value of Phase C current
Io
= 0.0
–
6553.5
A
RMS value of Zero Sequence Current (RMS Primary Amps)
I1
= 0
–
65535
%
Direct sequence
I2
= 0
–
65535
%
Inverse sequence
Tem
= 0 - 65535
%T
Actual temperature rise
SR
= 0
–
65535
%
Inverse sequence / Direct sequence