MHSC WDV500 Installation And Operating Instructions Manual Download Page 39

78D0011

39

WDV Series Gas Fireplace

safety Features

1.  Low Battery Detection 
  When low battery condition occurs, the transmitter will 

turn off the fireplace. 
A) Battery voltage is checked every one min-

ute.  When  the  battery  voltage  is  low,  the 
LCD displays a low battery icon which will 
exist in all modes.

B) The  transmitter  will  not  operate  with  low 

battery  voltage.  Change  the  batteries  be-
fore the batteries become too weak for normal op-
erations.  

2.  Power On Initialization
  After the power-on initialization, the transmitter sends 

a signal to turn off the fireplace.

3.  Thermal Shutdown
  When the ambient temperature is more than 99°F, the 

transmitter will turn off the fireplace. 
A) The LCD will display “HI”. 
B) The  Transmitter  will  not  function  until 

the room temperature has dropped be-
low 99 degree Fahrenheit. 

4.  Low Temperature Condition
  When  the  ambient  temperature  is  less 

than  40  degrees  Fahrenheit,  the  LCD 
will  display  “LO”,  and  NO  SIGNAL  will 
be sent to turn on the appliance.

  All  functions  still  remain  the  same  for 

both  Manual  Mode  and  Thermostat 
Mode

5.  Child-proof Protection 
  The child-proof icon will be shown when 

the  child-proof  mode  is  activated  by 
pressing  the  ON  button  and  the  OFF 
button  at  the  same  time  for  three  sec-
onds.
A) Enter childproof mode by pressing and holding both 

the  ON  button  and  the  OFF  button  simultaneous-
ly  for  3  seconds.  The  Childproof  indicator  will  be 
shown on the LCD.  

B) Deactivate childproof mode by pressing and hold-

ing the ON button and the OFF button simultane-
ously for 3 seconds again. The Childproof indicator 
disappears on the LCD.  

C) The  transmitter  cannot  be  operated  in  childproof 

mode.

tOuch screen reMOte cOntrOl OperatIOn

5.  When the light button is flashing, slide up and down on 

the arrow buttons will turn the light brightness to HIGH 
or Off directly without pressing the light button again to 
confirm

aux control (Optional)

The AUX  control  function  is  used  to  turn  on  or 
turn off the auxiliary component connected to the 
AC module of the Signature Command System. 
Press the AUX button to turn on or turn off the 
auxiliary.
1.  When the auxiliary is turned on, the icon will 

become solid text and the “ON” icon will appear below 
the “AUX” icon.

2.  When the auxiliary is turned off, the icon will become 

hollow text and the “ON” icon will disappear.

nOte:

 Some fireplaces use the AUX function to control 

options within the fireplace. Refer to fireplace manual for 
operation.

setting up Blank screen or constant Display in Idle

Figure 54

There is an option to set up how the LCD displays and 
functions  when  the  transmitter  is  in  idle.  There  are  two 
choices: 
1.  A)  Mode.  When 

the  transmitter  is 
in  idle,  the  icons 
in the “touch area” 
(timer, thermostat, 
blower,  light  and 
AUX)  will  disap-
pear, as shown in 
the  figure  on  the 
left.  When  any  of 
the  touch  buttons 
is  pressed,  those  icons  will  appear  and  are  ready  to 
operate (default). 

2.  B) Mode. The transmitter always displays all available 

icons  showing  current  status  of  timer,    thermostat, 
blower,  light  and AUX  as  shown  in  the  figure  on  the 
right.

Press TIMER and THERMO buttons at the same time for 

3 seconds to toggle between A) and B). 

1.  When the current setting is A), touch any place in the 

touch area to bring up the icons then press TIMER but-
ton and THERMO button at the same time for 3 sec-
onds. The backlight will flash once to indicate that the 
setting has changed to B).

2.  When the current setting is B), pressing TIMER button 

and THERMO button at the same time for 3 seconds 
will switch to A) Mode. The touch area icons will disap-
pear.

FP2658
AUX

FP2612
low battery

FP2613
HI

FP2614
lo no child

FP2659
blank screen

Figure 54

Summary of Contents for WDV500

Page 1: ...anual For assistance or additional information consult a qualified installer service agency or the gas supplier This appliance may be installed in an aftermarket permanently located manufactured home...

Page 2: ...tion Box Wiring 25 Command Center Wall Installation 25 Wall Switch Installation 25 SCS Wiring Diagram 26 Thank you and congratulations on your purchase of a MHSC Fireplace PLEASE READ THE INSTALLATION...

Page 3: ...by a qualified service person with glass door properly seated and sealed combustion leakage can occur CARBON MONOXIDE POISONING Early signs of carbon monoxide poisoning are similar to the flu with he...

Page 4: ...draw all combustion air from outside of the dwelling through the vent pipe These appliances have been tested by CSA and found to comply with the established standards for VENTED GAS FIREPLACES in the...

Page 5: ...tents for shipping damage and immediately inform your dealer if any damage is found Do not install any unit with damaged incomplete or substitute parts Check your packing list to verify that all liste...

Page 6: ...m 5 6M 146 mm 6 152 mm 8 1 6 2 0 8 0 m m 57 6 1470 mm 4 1 1 0 4 1 m m 57 6 1470 mm 35 6 905 mm Min Rough Opening Height 780012 DVW WDV dims 4656 1172 mm 8 6QE 211 mm Required Noncombustible Material A...

Page 7: ...on found in this manual for allowable venting configura tions These units can be installed in a bedroom Refer to the National Fuel Gas CodeANSI Z233 1 NFPA 54 current edition the Uniform Mechanical Co...

Page 8: ...3 mantel leg 156O 256O FP2423 Side of Fire place Opening Figure 5 Mantel clearances Top View Clearances to combustibles Follow these instructions carefully to ensure safe installation Failure to follo...

Page 9: ...h and optional fan must be done prior to final finishing to avoid costly reconstruction Only noncombustible materials i e brick tile slate steel or other materials with a UL fire rating of Zero may be...

Page 10: ...ved by MHSC Installation other than permitted by these instruc tions Venting INSTALLATION INFORMATION Read all instructions completely and thoroughly before attempting installation Failure to do so co...

Page 11: ...dditional pipe and elbows will be required You may use a chase with a vent termination with exposed pipe on the exterior of the house Refer to Installing A Vent System in an Outside Chase below If pip...

Page 12: ...y above the meter regulator assembly 5 m above the meter regulator assy I Clearance to service regulator vent outlet 3 91 cm 3 91 cm J Clearance to nonmechanical air supply inlet 6 15 cm for appliance...

Page 13: ...of the vent system 1 Determine the height of the center of the horizontal vent pipe exiting through the outer wall Using this dimen sion on the Sidewall Vent Graph below locate the point intersecting...

Page 14: ...the flue collars to the center of the wall opening Figure 12 Step 4 Using appropriate length of pipe section s attach to fire place with three 3 screws Follow with the installation of the elbow X X Fi...

Page 15: ...mounted to the top of the fireplace the maximum horizontal vent run before the termination or a vertical rise is 36 914 mm Figure 15 FP1176 max 90 bends Figure 14 Maximum Three 3 90 Elbows Per Install...

Page 16: ...he collar of the fireplace or transition elbow to the face of the exterior wall See the Sidewall Venting Graph for extended horizontal run if the vertical exceeds 12 1 Establish vent hole through the...

Page 17: ...ess Watertight Seal Around Pipe Sheet Metal Screws Wall Screws Snorkel WARNING Do not back fill around snorkel A clearance of at least 4 must be maintained between the snorkel and the soil Up to two 4...

Page 18: ...g to the position of the flue exit Mark the center point where the vent will penetrate the ceiling Drill a small locating hole a this point Drop a plumb line from the inside of the roof to the ceiling...

Page 19: ...combustible materials 6 Continue to add pipe sections until the height of the vent cap meets the minimum building code requirements NOTE You must increase vent height for steep roof pitches Nearby tr...

Page 20: ...exible vent pipe and push out of the way 3 Pull and extend the inner flexible vent 4 Slide the inner vent onto the adapter collar for a minimum 1C v overlap 5 Locate the clamp at approximately 3 4 fro...

Page 21: ...the flexible vent 5 Flexible vent spacers are to be installed at intervals prescribed by the flexible vent manufac turer and in such a way as to maintain concentric inner and outer vent spacing D Atta...

Page 22: ...sleet When using copper of flex connectors use only fittings approved for gas connections The gas control inlet is 3 8 NPT The gas control is equipped with a captured screw type pressure test point t...

Page 23: ...We recommend that you install a sediment trap drip leg in supply line as shown in Figure 33 Locate sediment trap drip leg where it is within reach for clean ing Install in piping system between fuel...

Page 24: ...ectrical Wiring General 1 This fireplace is equipped with the Signature Control valve which operates on 6 volts The A C module plugs into the fireplace junction box A C power supply Four 4 AA batterie...

Page 25: ...t extend beyond the 15 ft wire cable provided If a longer distance is required the 15 ft may be extended up to 30 ft maximum by using two 2 SCSWEK cables plugged together Route the wire from junction...

Page 26: ...Command Center Optional Wall Switch Plug in Connector Stepper Motor to Control Board DC Power Green Ground Plug in Connector Control Board to Solenoid Gas In Gas Out Pilot Gas Tubing Valve Light 300 W...

Page 27: ...ectly WARNING Electrical connections should only be performed by a qualified licensed electrician Main power supply must be turned off before connecting the fan to the main electrical power supply or...

Page 28: ...ove the front floor screen frame by unfastening the four 4 screws securing the front and sides 2 Install the six 6 halogen light bulbs provided Do not touch light bulbs directly with fingers 3 Replace...

Page 29: ...s are supplied with the 500 Series fireplaces Both bags should be used to cover the entire floor and burner Three 3 bags of glass are supplied with the 600 Series fireplaces It is not necessary to use...

Page 30: ...phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your finger to push in the master switch Never use tools If the switch will not f...

Page 31: ...as go to next step 4 Press the master switch to the ON position Within eight 8 seconds it will beep once This indicates the system is ready 5 Press ON button Sparker will spark and pilot flame will li...

Page 32: ...ut X LCD Backlight X Security Codes 16 X Countdown 6 hr Timer X Standard Thermostatic Control Mode X Smart Mode Thermostat Auto Flame Blower Modulation X Three Brightness Settings for Lights X Three S...

Page 33: ...button One beep for RF receiver ON or two beeps for RF receiver OFF will be given as confirmation Refer to Figure 57 for location 2 After the RF receiver is on holding the OFF button on the Command C...

Page 34: ...ff 3 Hold the OFF button anytime for three seconds or by turning off the wall switch These two commands of OFF are Memory Off the system will remember all last settings before turning off The next tim...

Page 35: ...an extended period of time Never leave anything on top of the surface of the transmitter FP2646 TSFSC display Information Bar Touch Area Logo Bar Menus Adjustment Controls Function Areas of the LCD Di...

Page 36: ...en and the green LED on the Command Cen ter will flash for 10 seconds WARNING Do not use two 2 or more remote control sys tems in the same area with the same privacy code setting as they will communic...

Page 37: ...Push and hold the TIMER button for 3 seconds Or b Use the OFF down buttons to decrease the Set Time to zero Or c Slide down on the arrow buttons to exit TIMER mode and shut off the fireplace Thermosta...

Page 38: ...off see blower On Delay and Off Delay in the next section 4 After the signal is sent the ON up and OFF down but tons become flame height controller again 5 When the fan button is flashing slide up and...

Page 39: ...flashing slide up and down on the arrow buttons will turn the light brightness to HIGH or Off directly without pressing the light button again to confirm AUX Control Optional The AUX control function...

Page 40: ...tteries 3 LCD display shows funny display 3 Reset the transmitter see Resetting the Transmitter section 4 Appliance does not come on 2 The transmitter did not match 1 Make sure the transmitter has wit...

Page 41: ...year Make sure the burner porting pilot air opening and burner air opening are free of obstructions at all times Pilot Flame The flames from the pilot should be visually checked as soon as the heater...

Page 42: ...cement glass door assemblies MUST be supplied by the fireplace manufacturer No substitute materials may be used Handle glass door with care to avoid striking or scratching it on hard objects To clean...

Page 43: ...Battery polarity wrong LED on the Command Center does not show solid green The 5 pin connector on the AC board broken or bent AC plug is plugged to AC mains Battery voltage low Using battery Check va...

Page 44: ...t 6 73D4521K 73D4521K 3 Glass Frame Assembly 1 78D0027K 78D1038K 4 Junction Box Assembly not shown 1 26D2128 26D2128 5 Panel Access Door 1 78D0040K 78D1046K Accessories Field Installed Options 6 Porce...

Page 45: ...78D0011 45 WDV Series Gas Fireplace REPLACEMENT PARTS SIGNATURE COMMAND SYSTEM 780012 DVW SG parts 6 09 1 2 3 4 15 5 6 7 8a 9 14 8b 8c...

Page 46: ...D0030 7 Injector 2 59D0062 69D0226 58D0051 20H3156 8a Burner Assembly 1 78D0033 78D0033 8b Burner Assembly 1 78D1058K 78D1058K 8c Burner Assembly 1 78D1057K 78D1057K 9 Venturi 2 69D1026 69D1026 69D102...

Page 47: ...ones REPLACEMENT PARTS Item Description 500 Qty 600 Qty Part No 1 White Stone 1 5 5 78D0122 2 Light Gray Stone 2 5 5 78D0123 3 Dark Gray Stone 3 5 10 78D0124 4 Brown Stone 4 5 5 78D0125 5 Sand Stone 5...

Page 48: ...48 78D0011 WDV Series Gas Fireplace HOT 1 2 3 4 5 6 9 7 8 10 730024 KHLDV vent parts VENT components REPLACEMENT PARTS...

Page 49: ...A VC 1280 5DT VC 3 4 6 Pipe Length 58DVA 06 1208 5DT 06 3 4 9 Pipe Length 58DVA 09 1207 5DT 09 3 4 12 Pipe Length 58DVA 12 1206 5DT 12 3 4 24 Pipe Length 58DVA 24 1204 5DT 24 3 4 36 Pipe Length 58DVA...

Page 50: ...rdance with the above provisions shall comply with NFPA 720 and ANSI UL 2034 listed and IAS certified Signage A metal or plastic identification plate shall be permanently mounted to the exterior of th...

Page 51: ...time Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox burner assembly dam...

Page 52: ...149 Cleveland Drive Paris Kentucky 40361 www mhsc com Based on CSA P 4 1 09 Efficiency Ratings Model EnerGuide Ratings Fireplace Efficiency WDV500NTSC 64 4 WDV500PTSC 67 7 WDV600NTSC 70 2 WDV600PTSC...

Reviews: