26
STRATA2
5.9 connecting a condensate pump
If a suitable drain for condensate disposal is located too high to be able to discharge the condense
water from the boiler, a condense pump must be installed within the base of the boiler.
This condensate pump has a built-in safety device. If the pump outlet is blocked, the water level in the
pump reservoir will rise to just below the rim – if the level rises any further, the power to the boiler will be
switched off.
At the right hand side, in the area of the boiler base, there is a socket – if no condensate pump is used,
there will be a plug with a control link in place. The condensate pump (KHP1) must be wired into this plug
once the link wire has been removed.
condensate receptacle & pump
model No. KHPI
KHPI
Blue - Neutral
Brown 230V Live
“out” to boiler interlock.
Supply fails if condense
level too high
Black Permanent Live 230V
Remove Link
Strata 2
Condense
Pump Plug
N
I
L
Fig 5.9a
5.8.3 mixing valve controller RVA 46 installation
procedure
Complete the following steps to install the RVA 46:
●
Remove the blank panel beside the manager.
●
Unpack the RVA 46 and insert it in the opening of the control panel.
●
Place the wiring harness with 7-pin connector in the bottom of the RVA 46 and click the other end into
the wiring upstand at the rear of the boiler.
●
Place the wiring harness with the 6-pin connector in the top of the RVA 46 and click the other end into
the wiring upstand at the rear of the boiler.
●
Connect the controller power supply from RVA 47 loom.
●
Connect LPB circuit (pink and mauve) from RVA 47 loom.
The following can now be connected if necessary:
P1
Pump for mixed circuit
Brown
M1
Three way mixing valve
Brown
AF1
Outside air sensor
Black
RE1
Room unit or thermostat
Light-blue
VF1
Mixed flow sensor
White
Table 6