22
REGENCY2
L O W
P R O F I L E
6.0 fault
finding
IS THE GAS COCK OPEN
AND THE CORRECT
INCOMING GAS SUPPLY
PRESENT? DEPENDING ON
TYPE OF GAS USED
START
CHECK
INCOMING
POWER SUPPLY
& FUSE
IS THERE POWER
TO THE BOILER?
DOES THE
BOILER ATTEMPT
TO LIGHT?
DOES THE
CONTROL BOX
GO TO
LOCKOUT?
IS THERE
POWER TO THE
CONTROL BOX?
CHECK AND
REPLACE FUSE
IF REQUIRED
IS THE
MAINS SWITCH
ILLUMINATED?
ADJUST
THERMOSTAT AND
CHECK EXTERNAL
CONTROL SIGNAL
IS THE BOILER
BEING CALLED TO
OPERATE VIA THE
CONTROL SIGNAL
OR THERMOSTAT?
SWAP PHASE
AND NEUTRAL
IS THE INCOMING
SUPPLY POLARITY
CORRECT?
CHECK POWER
TO THE CONTROL
BOX AND REPLACE
IF REQUIRED
HAS THE OVER TEMP
STAT OPERATED?
HAS THE FLUE LIMIT
STAT TRIPPED?
HAS THE CONTROL
BOX LOCKED OUT?
RESET VIA
THERMAL RESET
RESET STAT
IS THIS ON FIRST
POWERING UP
THE BOILER?
CHECK IGNITION
ELECTRODE
CHECK BURNER
PRESSURE
CHECK IGNITION
LEADS/CONTINUITY
INVESTIGATE CAUSE
OF THE TRIP
I.E. PUMP FAILURE/
BLOCKED HEAT
EXCHANGER
INVESTIGATE CAUSE
OF TRIP I.E. SPILLAGE/
VENTILATION ETC.
RESET - FULLY AUTO
BOILERS ARE SUPPLIED
IN LOCKOUT STATE
DOES THE GAS
VALVE(S) OPEN?
CHECK POWER
TO GAS VALVE
AND REPLACE
IF REQUIRED
NO
NO
YES
NO
NO
NO
NO
NO
NO
YES
YES
NO
NO
YES
YES
YES
NO
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES