Heating Curve Slope
0.10 - 4.00
1.50
3.20
-
1021
Heating Curve
Displacement
-4.5 - 4.5
0.0
°C
1026
Heating Curve
Adaption
Off - On
Off
-
1030
Summer/Winter
heating limit
---/8
– 30
18
°C
1032
24-Hour heating limit
---/-10
– 10
-3
°C
1033
Ext’n 24-Hour heating
limit
Yes
– No
Yes
1040
Flow temp setpoint
min
8
– P1041
8
°C
1041
Flow temp setpoint
max
P1040
– 95
85
°C
1042
Flow temp setpoint
room stat
---/P1040 - ---/P1041
---
°C
1044
Swi-on ratio room stat
---/1
– 99
---
%
1046
Delay Heat request
0
– 600
0
S
1050
Room Influence
---/1
– 100
---
%
1060
Room temp limitation
---/0.5
– 4
1
°C
1061
Heating limit room
controller
---/0
– 100
---
%
1070
Boost heating
---/0
– 20
5
°C
1080
Quick setback
Off, Down to Reduced Setpoint,
Down to Frost Protection Setpoint
To Reduced
Setpoint
-
1090
Optimum start control
max
0
– 360
0
Min.
1091
Optimum stop control
max
0
– 360
0
Min.
1094
Heat up gradient
0
– 600
60
Min/k
1100
Reduced setp.
increase start
---/P1101
– 10
---
°C
1101
Reduced setp.
increase end
-30
– P1100
-15
°C
1109
Continuous pump
operation
No
– Yes
No
1112
Frost protection flow
temp.
Off
– On
On
1120
Overtempprot. pump
circuit
Off
– On
On
-
1130
Mixing valve boost
0
– 50
5
°C
1132
Actuator type
Two Position
– Three Position
Three-position
-
1133
Switching differential
2-pos
0
– 20
2
°C
1134
Actuator running time
30
– 873
120
S
1135
Mixing valve Xp
1
– 100
32
°C
1136
Mixing valve Tn
10
– 873
120
S
1150
Floor curing Function
Off, Function heating, Curing heating,
Fu Curing heating,
functional heating, Manually
Off
-