Pressure Leak Test

A. The instrument is power on with the blue and red valves turned off.

B. Press the Function button to pressure leak test mode shown as below. The current pressure value is displayed at lower 
right corner of LCD.

C. Press the Run/Stop button to start the leak test, as shown below:

At this time, the lower left corner records the initial pressure value; the 
lower right corner shows the instantaneous pressure value; the “ΔP” 
display area shows the difference between initial pressure value and 
instantaneous pressure value.

The time display area shows how long the leak test lasts in the format of 
Hour : Minute (HH:MM). All the pressure units on the screen are the 
same. You can switch different pressure units by pressing the unit button.

 

 

Common problems

Common problems

Low battery power supply

The instruments has low power sign. When it is displayed , it means the battery power is insufficient. At this time, the battery 
should be replaced as required in order to avoid affecting normal use.

Damaged refrigerant hose or valve stem

Please check the pipe fittings and the hoses before testing. Once any damage is found , please replace it immediately to 
avoid improper use or any accident occurring.

Failure of refrigerant filling

There is a valve core in the refrigerant inlet of the refrigeration system. When connecting the instrument, pay attention to 
the two terminals of the hoses. Connect one terminal with a core to the refrigeration system, while another terminal without 
a core to the instrument.

Potential leak points

- Every hose terminal comes with a nylon pad that is limited a certain life of using. Over use or other situation will make it 
defective, which result in leakage.
- The instrument refrigerant inlet (the middle port of the instrument ) has a port with valve core , which is used to vent the 
air in the hoes after connecting the refrigerant to the instrument.
The port is equipped with a copper plug screw. It is required to tighten it every time before or after operation.
- Check the refrigeration system's pipes and connectors.

7

MGF

MGF

 srl –– Via Chico Mendes, 8 – 43058 Sorbolo Mezzani (PR) Italy –

 

Tel. +39 0521-818301 Fax: +39 0521-818202

e-mail: [email protected] – 

www.mgftools.com

  

www.nebulizzare.com

Summary of Contents for 930780

Page 1: ...ico Mendes 8 43058 Sorbolo Mezzani PR Italy Tel 39 0521 818301 Fax 39 0521 818202 e mail info mgftools com www mgftools com www nebulizzare com Art 930780 Digital manifold pressure tester User Manual Rev 1 dated 15 04 2021 ...

Page 2: ...storage The instrument has double pressure sensors dual temperature probes digital readout multiunit switching multi mode function and built in refrigerants database The instrument uses high strength engineering plastics and flexible non slip silicone design the whole machine is solid and comfortable to hold Built in 32 bit digital processing unit and high precision data acquisition unit high data...

Page 3: ... and store the instrument in high temperature high humidity flammable explosive and strong electromagnetic fields 7 Please do not change the instrument internal circuit to avoid any damage of the instrument or danger occurring 8 Please wear qualified protective equipment to protect user during testing 9 Please use the instrument in a well ventilated environment to prevent inhalation of toxic gases...

Page 4: ... and description Icon and description 1 Clamp on temperature probe socket 2 Clamp on temperature probe socket 3 LCD display 4 Run Stop button In Leak Test Mode Test Control Button 5 Function button test function mode switch button 6 R R Refrigerant Type Selection Buttons Switch to select different types of working refrigerants 7 Unit button pressure unit switch button 8 C F button temperature unit...

Page 5: ... refrigerant into the refrigeration system Vacuum operation is required if it is filled initially or in full with refrigerant Refer to the section on vacuum operation J After the filling is completed shut the low pressure valve blue valve and refrigerant valve Let the refrigeration system running K Shut down the refrigeration system make sure all valves are turned off then disconnect the instrumen...

Page 6: ...ump Turn off the blue valve and red valve B Power on the instrument Then make sure if the LCD displays vacuum test status as below picture If not press the Function button to switch it C Press the unit button to adjust the reading unit D When the instrument is turned on there may be 10 digits in the high and low pressure display area At this time press the zero button long until it returns to zero...

Page 7: ...ged refrigerant hose or valve stem Please check the pipe fittings and the hoses before testing Once any damage is found please replace it immediately to avoid improper use or any accident occurring Failure of refrigerant filling There is a valve core in the refrigerant inlet of the refrigeration system When connecting the instrument pay attention to the two terminals of the hoses Connect one termi...

Page 8: ...n the surface of a container or object is called absolute pressure the absolute pressure value is absolute vacuum as a starting point the symbol is PABS ABS is a subscript and the absolute pressure is atmospheric pressure gauge pressure At atmospheric pressure the gauge pressure is 0 and the absolute pressure is 1 013 bar Dry bulb temperature wet bulb temperature and black ball temperature Dry bul...

Page 9: ...ue of which is expressed in W W COP under rated operating conditions high temperature and specified conditions when the airconditioning heat pump heating operation the ratio of heating and effective input power the value of W W 9 MGF MGF srl Via Chico Mendes 8 43058 Sorbolo Mezzani PR Italy Tel 39 0521 818301 Fax 39 0521 818202 e mail info mgftools com www mgftools com www nebulizzare com ...

Page 10: ...wn responsibility that the Digital manifold pressure tester art 930780 is in conformity with the following standards or standardized documents EN 61326 1 2013 MGF MGF srl 10 MGF MGF srl Via Chico Mendes 8 43058 Sorbolo Mezzani PR Italy Tel 39 0521 818301 Fax 39 0521 818202 e mail info mgftools com www mgftools com www nebulizzare com ...

Reviews: