![MGE UPS Systems STS 400A Installation And User Manual Download Page 51](http://html.mh-extra.com/html/mge-ups-systems/sts-400a/sts-400a_installation-and-user-manual_1783029051.webp)
Installation and User Manual
Operation
3 —13
86-504004-00 B03
Figure 3-4: LED Mimic Diagram.
SOURCE #1
AVAILABLE
GREEN LED-LIT
WHEN SOURCE #1
POWER IS APPLIED
TO SOURCE S1 INPUT
SOURCE #2
AVAILABLE
GREEN LED-LIT
WHEN SOURCE #2
POWER IS APPLIED
TO SOURCE S2 INPUT
OUTPUT POWER
TO LOAD
GREEN LED-LIT
WHEN OUTPUT
POWER IS ON
STS OUTPUT
ISOLATION C.B.
(CB3A AND/OR CB3B)
GREEN LED-LIT
WHEN CLOSED
SOURCE #1
INPUT C.B.
GREEN LED-LIT
WHEN CLOSED
SOURCE #1
BYPASS C.B.
GREEN LED-LIT
WHEN CLOSED
STATIC SWITCH #1
GREEN LED-LIT
WHEN SCR1 ON
SUMMARY
ALARM-RED LED
SOURCE #2
INPUT C.B.
GREEN LED-LIT
WHEN CLOSED
SOURCE #2
SELECTED AS
PREFERRED-
YELLOW LED
SOURCE #1
SELECTED AS
PREFERRED-
YELLOW LED
SOURCE #2
BYPASS C.B.
GREEN LED-LIT
WHEN CLOSED
STATIC SWITCH #2
GREEN LED-LIT
WHEN SCR2 ON
IN SYNC-
GREEN LED
SOURCE 1
AVAILABLE
SOURCE 2
AVAILABLE
PREFERRED
SOURCE
IN SYNC
ALARM
LOAD
SWITCH 1
SWITCH 2
CB5
CB4
CB3
CB1
CB2
S1
S2
Summary of Contents for STS 400A
Page 2: ......
Page 28: ... This page left blank intentionally Epilson STSTM 1 12 86 504004 00 B02 ...
Page 54: ... This page left blank intentionally Product Name 3 16 86 504004 00 B02 ...
Page 58: ... This page left blank intentionally Product Name W 4 86 504004 00 B02 ...
Page 62: ... This page left blank intentionally Epilson STSTM G 4 86 504004 00 B03 ...
Page 64: ......
Page 65: ......