3. Operation
"ECO mode" tab
ECO mode is not possible unless it has first been authorized using the "UPS Driver" software
3.6 Shutdown
1. Press button (return to the OFF position).
The connected equipment is no longer supplied with power.
2. Set the battery circuit breaker(s) to OFF.
The battery is no longer recharged.
Fig. 3
Personalizable function
ECO mode authorization
Authorized voltage range for
operation in ECO mode (see figure 3)
Default setting
Disabled
(not authorized)
200 V to 240 V
(for 230 V rated
voltage)
Options
Enabled (click to check)
The upper threshold (max. voltage) is between
the maximum authorized voltage for transfer to
the bypass and the rated voltage.
The lower threshold (min. voltage) is between
the minimum authorized voltage for transfer to
the bypass and the rated voltage.
8
24
24
8
Range for minimum authorized
voltage for operation in ECO mode
Range for maximum authorized
voltage for operation in ECO mode
Minimum authorized voltage
for transfer to the bypas
Maximum authorized voltage
for transfer to the bypass
Voltage in V
Rated
voltage