4.2 Replacement of the battery module
4. Maintenance
Removal of the battery module
This operation may be carried out with the UPS supplying power to the load.
Safety rules
Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high. Precautions
must be taken for all handling:
◗
remove all watches, rings, bracelets and any other metal objects;
◗
use tools with insulated handles.
A
- Use a finger to unclip the small plate
with the MGE logo on the front panel of the
UPS.
B
- Remove the two screws.
C
- Pull away the left-hand side of the front
panel.
D
- Remove the screw securing the safety
connector.
E
- Remove the safety connector.