Getting Maximum Battery Life From the
Pulsar Eclipse Plus 250
1.
Prior to first use, charge the Pulsar
Eclipse Plus 250 battery for 8 hours.
This helps condition the battery for long
life.
2.
After a complete discharge, a few hours
are required to reach full recharge.
Notes:
1. Pulsar Eclipse Plus 250 is equipped with a
12V/4.2Ah lead acid battery, which must be
disposed of in accordance with local
regulations. MGE will accept UPS and/or
batteries for recycling free of charge. Contact
us at the phone number shown in the
recycling section of this manual.
2. Battery life is cut in half for every 15
degrees above 75°F. Plug in and recharge the
UPS at least every six months if the UPS is
taken out of service and not plugged in.
ID Labels and Cable Organizers
Eclipse Plus 250 includes ID labels to label
each item plugged into the UPS. Simply peel
off the label which matches the device you
have plugged in (or type the name on the
blank labels) and attach it to the recess next
to the outlets. Attach the matching label to
the cord of the device. In this way, you can
always return each device to its proper
location should you need to remove it.
The cable organizers are provided to “clean
up" the installation. Locate the cable
organizer where it will restrain the cables to
the UPS in optimum locations. Clean the
location where the organizer will be mounted
to remove any traces of oil or dirt. Remove
the covering on the self-adhesive backing.
Press into position and allow to set overnight
for adhesion to properly set. Be sure to
attach organizer when temperatures are
above 70°F. Press cables into organizer and
close cover.
Battery Replacement
Caution: read and follow safety instructions
before removing batteries. This must be done
by knowledgeable personnel due to risk of
electric shock and high energy.
1.
In accordance with local regulations and
proper disposal of Pulsar Eclipse Plus
250 battery(s), it is necessary to remove
them from UPS chassis for recycling and
replacement.
2.
Turn off and unplug UPS and all critical
devices.
3.
Open the door located on the bottom of
the UPS. A torx T15 screwdriver is
required for this procedure.
4.
Remove screw and follow operations
described in Figure 4 to open the door
and slide out the battery.
5.
Unplug the battery for replacement.
Replace with only exact matching
battery available from MGE.
6.
Insert new battery and reconnect.
7.
Close door and reinstall screw.
8.
Plug in UPS to utility power and all
critical devices. Restart.
Sizing Guide
"Computer Outlets"
Monitor
Back up Time
486, Pentium, Celeron,
14, 15" monitor
10 minutes
Pentium Pro, K6
iMac
14, 15 " monitor
8 minutes
486, Celeron, Pentium,
16, 17" monitor
7 minutes
Pentium Pro, K6
Pentium II, Pentium III
14, 15" monitor
5 minutes
Pentium II, Pentium III
17" monitor
3 minutes
Back up Time
Load Back
up
Time
50 VA
30 minutes
100 VA
21 minutes
150 VA
10 minutes
200 VA
7 minutes
250 VA
5 minutes
Product Specifications
UPS rating: 250 VA/168 W (2.1 A)
Battery: 1 system, 12 volt/4.2 Ah
Surge suppressor rating: 950 VA (8 A)
Battery life: 5 years with normal use
Input voltage: 120 VAC, 50/60 Hz
Operating temperature: 32 – 104°F up to 1500M
Output voltage: 120 VAC 50/60 Hz
Storage temperature: -5 – 122°F
UPS back-up time: 5-30 minutes
Size: 10" L X 7" W X 2.6" H
UPS output wave shape: Modified sine
Weight: 6.6 lbs.
Surge suppressor joule rating: 450
Warranty: 2 years parts and labor
Input cord: 6 foot with NEMA 5-15 plug
Accessories: ID labels, cable organizers,
Circuit breaker: 10 amp
fax/modem cable
UPS (on battery) current limit: >250 VA
Agency: UL, cUL, FCC
Recharge time: 8 hours
Troubleshooting
UPS has no output and no LED display
Check to be sure UPS is plugged in,
AC power is "on" to UPS and UPS is
turned "on".
UPS has little or no back-up time
Charge UPS overnight and retry. After
3-5 years, consider replacing batteries if
back-up time is short.
UPS transfers to battery, flashes green
Many low voltage events or poor voltage
and audible alarm beeps often
regulation at receptacle. Try another
receptacle.
LED lights red, continuous audible alarm
Potential internal failure. Restart UPS, if
red LED reappears. Call for assistance.
LED flashes red twice a second with beep
UPS lightly or heavily overloaded. Reset
twice a second
circuit breaker on UPS if necessary.
Reduce load and restart UPS.
MGE maintains a phone number for technical support for US and Canadian customers. Call
for assistance as shown in the "Service and Parts" section of this manual or visit our web site
at: www.mgeups.com
MGE UPS Systems
86-153538-00
page 4
MGE UPS Systems
Eclipse Plus 250 User’s Manual
page 5
Instructions for Operation
Battery door
Battery access screw
Fax/Modem
protector
in
out
Figure 4