Best performance UPS -
Comet EX RT
140, avenue Jean-Kuntzmann
ZIRST - Montbonnot Saint-Martin
38334 Saint-Ismier Cedex - France
Tel. +33 (0)4 76 18 30 00
CEXRT448UK - 02/05
Power management
Solution-Pac 2 software suite on CD
Supplied as standard to assure the local
or remote supply to the servers.
Optional Network Management Card
Connect to Ethernet, alarms and
supervision using a Web-interface.
Environment Sensor for SNMP / Web
card
SNMP and Web monitoring of temperature
+ RH + status of 2 contacts
Monitoring using Enterprise Power
Manager or the NMS
Supervision through Enterprise Power
Manager or NMS integration kit :
HP Openview, Tivoli Netview,
CA Unicenter.
Monitoring using Enterprise Power
Manager or the integration kit
Jbus/Modbus card
For connecting the UPS to a building
management system.
Slot for MGE inter-unit
communication card
9-pin D output
connector
RJ11 port for remote
emergency power off
Connectors for
automatic detection
of battery module(s)
RS 232
communication
port
Connector for
supplementary
battery module
power cable
Manual bypass for
hot maintenance
Output connectors
Source switch 1
Source 1 connector
Source 2 connector
Battery circuit breaker
Multilingual back-lit rotating display
Powered
equipment
Battery
mode
Bypass
mode
Main
alarm
32-character
LCD
As standards and equipment may change, the characteristics described in the text and the images in this document are not bindin
g unless confirmed by us. All brands mentioned are the property of their respective owners.
Published by: MGE UPS SYSTEMS, (January 2005) - Designed by: Pample33 4 79 37 87 66 - Updated by MGE UPS SYSTEMS, Graph
ical Studio - Translation: TTP: +33 4 78 66 47 99
9
10
11
12
8
7
6
5
4
3
2
1
Specifications
Part numbers
5 kVA
7 kVA
11 kVA
Performances
Active power kVA / kW
5 / 4
(1)
7 / 4.9
11 / 8
Technology
on-line double conversion with PFC (Power Factor Correction) system
(2)
)
Rated input voltage
200/208/220/230/240/250V single phase
380/400/415V three phase
Input voltage range
(- 30 %; + 20 %) 230 V ; (-20 %, + 15 %) 400 V
Input, output frequency range
40-70 Hz, 50 / 60 HZ autoselection, frequency converter as a standard
Output voltage / THDU
200/208/230/240 /250 V +/- 2 %; THDU < 2 %
Overall efficiency
normal mode 91 %, eco mode 97 %
THDI
THDI < 5 %
(3)
Crest factor / short circuit current
3:1 / 100 A
3:1 / 150 A
Overload capacity
>150 % 500 ms; 150 % 30 s; 125 % 60 s; 110 % 120 s
Temperature operating
45°C for 8 Hrs
(4)
, 40°C continuous
Back-up times
(5)
at 70 % load
from 10 up to 15 minutes
Standard : 1 power mod. 3U + 1 battery mod. EXB 3U = 6U
from 15 up to 20 minutes
St 1 battery mod. EXB 3U = 9U
from 40 up to 65 minutes
St 2 battery mod. EXB 3U = 12U
Connection
Input /output
terminal block for 13 mm
2
(stranded cable) or 10 mm
2
(solid cable)
Communication
Port type
6 voltage free contacts DB9 2 A 48 V DC, 1 RS 232 ,
RJ11 for remote emergency power off
Slot
1 slot for MGE inter-unit communication card
Standards and certification
Performance and safety
IEC 62040-1/IEC 60950/UL 1778 and CSA 22.2
(
2)
EMC
IEC 62040-2; EN 50091-2; FCC class A
(2)
, EMC B level
(6)
Certification
UL
(2)
/TÜV , GS mark,CB, C-Tick,CE, IEC 68-2-6 (vibration tests Marine approval)
Dimensions (H x W x D) in mm; weight (single phase input / three phase input)
Comet EX RT standard backup tower
444,5 x 261,2 x 700
89,5 Kg
88,3 Kg / 89,5 Kg
94,2 Kg / 95,3 Kg
Comet EX RT standard backup Network Pack
261,2 (6U) x 444,5 x 700
rack mounting
97,3 Kg
96,1 Kg / 97,3 Kg
102 Kg / 103,1 Kg
Comet EX RT Power module
444,5 x 130,6 x 700 / 130,6 (3U) x 444,5 x 700
24,2 Kg
23 Kg / 24,2 Kg
24,9 Kg / 26 Kg
Battery module Comet EXB RT
444,5 x 130,6 x 650 / 130,6 (3U) x 444,5 x 650
64,5 Kg
64,5 Kg
68,5 Kg
EX RT CLA module / EX RT Transformer
130,6 (3U) x 444,5 x 650 / 12 Kg / 87 kg
Ratings
5 kVA
7 kVA
11 kVA
Input voltage
single-phase three-phase
single-phase
three-phase
single-phase
three-phase
Comet EX RT standard back-up time Tower
-
68 054
68 070
68 074
68 110
68 114
Network Pack Rack Format (7)
-
68 056
68 072
68 076
68 112
68 116
EXB RT battery module / EXB RT battery module
-
68 078 / 68 079
68 118 / 68 119
with EPO built-in
Comet EX RT Power module
-
68 057
68 075
68 077
68 115
68 117
(for use with EXB or CLA module)
Rack kit for Comet EX RT Power module /
Comet EXB RT and CLA
-
68 001 / 68 002
EX RT Transformer module
-
68 003
Comet EX RT CLA module (2 to 8 hours)
-
68 004
EX RT Battery Integration System (8)
-
68 005
EMC B level filter module
-
-
68 008 - 68
008 -
Comet PDU 19" rack format (9)
-
66 857
1.8 m battery connection cable (10)
-
68 006
UPS Control, remote UPS monitor display
-
66 080
1:
single phase input not available for 5kVA.
2:
applicable to single phase models.
3:
single phase input value.
4:
at nominal output
power for 230 V or 400V input and 230V output.
5:
typical values after 3 discharge cycles, batteries 3-5 years, longer backup times
available using the CLA or EXB module, ask for details.
6:
option for single phase model.
7:
the Network Pack version comprises
standard back-up time unit + Network Management Card + rack mounting kit
8:
trolley capacity 8 modules max, casters, adjustable feet.
9:
12 sockets 4 X IEC 16 A + 8 X IEC 10 A.
10:
for non standard inter-module spacing.
10
11
12
4
5 3
2
1
6
6
8
7
9
MGE PowerServices™
1-year warranty, including battery.
Associated services
(1)
◗
Warranty extension
◗
Commissioning: startup of your
installation conforming to the
manufacturer’s specifications.
◗
Teleservice/ E Teleservice: remote
monitoring via the telephone
system/Internet.
◗
Maintenance contracts: a range of
convenient maintenance programmes.
◗
Site audit: load analysis and
recommendations in line with the
technical environment.
1: Depending on the country, visit www.mgeups.com/services.