34007724EN/AA
- Page 25
BY
PASS
NORMAL
_
+
N
L
BATTERY
AC INPUT
2. Installation
Connection of CLA module
AC Input
To battery
29
28
◗
Connect the battery cable
28
(provided with the
CLA
module) between the power module and the
CLA
module.
◗
Connect the cable
29
(provided with the
CLA
module) between the power module and the
CLA
module.
◗
Connect the battery:
◗
Cable cross-section (not provided): 10 mm
2
, solid or stranded wire (maximum 13 mm
2
or AWG 6).
◗
Use a circuit-breaker (curve B, 50 A) for cable protection.
◗
Connect the input cable of the
CLA
module to the AC input:
◗
AC input cable cross-section (not provided) : 2,5 mm
2
.
◗