4.4 UPS Set-Up
Local Settings
Output Settings
ON/OFF Settings
Function
Factory Setting
Options
Comments
Cold Start
Disabled
Enabled
Start on battery
Forced Reboot
Enabled
Enabled
Enables automatic restart of the
system even if Normal AC source
is restored before the end of the
shutdown sequence
Auto Restart
Enabled
Disabled
UPS restarts automatically when
Normal AC source is restored
Energy Saving
Disabled
Enabled
Automatic shutdown on battery if
output load level < 10%
Sleep Mode
Enabled
Disabled
Remote Command
Enabled
Disabled
Enables consideration of
shutdown or restart orders from
software to be authorized
Function
Factory Setting
Options
Comments
Output Voltage
208V
200V / 230V / 220V /
240V / 250V
Freq Converter
Disabled
Enabled
Output Frequency
60 Hz
50 Hz
User selectable under frequency-
converter mode
Eco Mode
Disabled
Enabled
See glossary
Slew rate
1 Hz/sec.
0.5 Hz/sec.
Bypass Transfer
Yes
No
Transfer to bypass if Normal AC
source is out of tolerance
Interrupt Time
10 ms
20 ms, ...... , 200 ms
Break time calibration during load
transfer on Normal AC source out
of tolerance
Overload Prealarm
105 %
40%, 50%, 70%
Alarm if threshold is overrun
Function
Factory Setting
Options
Language
English
French, German, Italian, Portuguese, Spanish
Date/Time Format
International format
(DD-MM-YYYY/HH :MM)
US (MM-DD-YYYY/HH:MM AM/PM)
Date/Time Change
GMT + 1
(Continental Europe)
MM-DD-YYYY/HH :MM adjustable
Audible Alarm
Yes
No
Pulsar MX
Access to Maintenance and
Personalization Data
4 — 2
86-87050-00 A01
Summary of Contents for 5000 RT
Page 2: ......
Page 4: ...Pulsar MX 86 87050 00 A01...
Page 10: ...This page left blank intentionally Pulsar MX 4 86 87050 00 A01...
Page 30: ...This page left blank intentionally Pulsar MX 4 4 86 87050 00 A01...
Page 36: ...Pulsar MX 86 87050 00 A01...
Page 40: ...Pulsar MX 86 87050 00 A01...
Page 42: ...Notes Pulsar MX 86 87050 00 A01...
Page 43: ......