Indication
Diagnostic
Correction
LED
27
flashes and UPS overload. Overload is too long or too high.
◗
Check the power drawn by the
the buzzer beeps.
◗
If AC power is present and within tolerances, the
equipment and disconnect any
UPS goes to bypass mode (supply directly by the
non-priority devices.
AC-power source). LED
19
flashes.
The buzzer beeps every second.
◗
If AC power is not present or not within tolerances,
the connected applications are no longer supplied.
The buzzer sounds continuously.
LED
25
flashes and A battery fault was detected during the
◗
Check that the battery connector
the buzzer beeps.
automatic battery test.
is fully pushed in.
◗
Replace battery module (see Maintenance section).
LED
25
flashes and
The battery has reached the theoretical end
◗
Reset the alarm by pressing
the buzzer emits a
of its service life.
buttons
22
and
23
long beep once
simultaneously for 3 seconds.
per hour.
◗
It is advised to replace both batteries at
See the section on maintenance.
the same time with the same rating
as the original batteries.
The yellow LED
24
The function for monitoring the phase and neutral
◗
Directly earthed neutral type
flashes, the red
position of your electrical network has detected a
networks: check the cabling
indicator light
11
reversal.
of phase and neutral on your
behind the UPS
electrical network
.
comes on and the
For all other network types,
buzzer sounds
de-activate the detection function
continuously.
(this function is only operational
for directly earthed neutral electrical
networks):
Press for at least 5 seconds the
pushbutton
10
behind the UPS
(UPS stopped and connected to the
network for less than 30 minutes).
Page 20 -
3400753300/AE
If any of LEDs
25
,
26
or
27
flash, there is a operating anomaly or an alarm.
NOTE: If a LED flashes, the bargraph data is no longer displayed.
4.1 Troubleshooting
4. Maintenance