8 – Door Control AS 210 B / Rev.A 2.0
5.6 Connection examples in connection with
the ZM-SKS B plug-in module (terminal X3)
For optoelectric closing edge safety device
- DIP switch 1 must be set to the OFF position.
For 8.2 kOhm closing edge safety device
- DIP switch 1 must be set to the ON position.
For pneumatic closing edge safety device
- An 8.2 kOhm resistance must be connected in series with
the pressure switch.
- DIP switch 1 must be set to the ON position.
- DIP switch 2 must be set to the ON position.
wt: white
gr: green
br: brown
Initial operation
8,2
8,2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
+12 V
Sig
GND
br
gr
wt
5.5 Connection examples for command and
safety devices (terminal block X3)
OPEN / STOP / CLOSE buttons
(4-lead solution)
- STOP button
- OPEN button
- CLOSE button
Key switch OPEN / CLOSE
- OPEN button
- CLOSE button
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15