MEWOI MEWOI1500D Manual Download Page 14

 

 

-10- 

continually,  press  the  POWER  key  to  make  HV  detector  in 

continuous  running,  and  then  press  the  POWER  key  again  to 

power off. 

2. Power-on/off of principal machine   

Press  the  POWER key  to  power  on,  then  LCD  begins  to  display, 

the  principal  machine  enters  the  test  and  receiving  mode  after  a 

normal booting (see below), 1st means the measured data of the 

primary  circuit  on  HV  terminal,  2nd  means  the  measured  data  of 

the  secondary  circuit  on  LV  terminal,  F.  Er  means  the  error 

between  the measured  CT  ratio  and  preset  CT ratio,  R,  S,  and T 

means the three phases respectively,    and the data measured by 

LV current clamps of CT1, CT2, and CT3 can be displayed on the 

position of R, S, and T on screen respectively. the LCD can display 

the 

symbol “- - -” if the principal machine doesn’t receive the signal 

from  primary  circuit;  the  principal  machine  can  detect  the  phase 

and  polarity  firstly,  if  receives  the  data  of  the  primary  and  the 

secondary  circuit  normally,  the  primary  circuit  currents  are 

correspondingly visible on the phases of R, S, and T, both the error 

and polarity can be displayed on the upper left corner of LCD. If the 

symbol “Err” displays on the upper left corner of LCD display, it is 

not  available  to  detect  the  polarity  properly,  and  the  measured 

currents  of  the  primary  circuit  remain  being  displayed  on  the 

R-phase. 

 

 

 

 

Summary of Contents for MEWOI1500D

Page 1: ...MEWOI1500D THREE CHANNEL WIRELESS HV CT RATIO TESTER WWW MEWOI COM...

Page 2: ......

Page 3: ...8 V OPERATIONS 9 1 POWER ON OFF OF HV DETECTOR 9 2 POWER ON OFF OF PRINCIPAL MACHINE 10 3 TEST OF HV CURRENT 11 4 TEST LV CURRENT 14 5 TEST OF CT RATIO POLARITY 16 6 DETECTION ON PHASE SEQUENCE 20 7 A...

Page 4: ...12 DATA UPLOAD 22 VI SETTINGS 22 1 SET CT RATIO 23 2 SET ERROR 23 3 SET TIME 24 4 SET BACKLIGHT 24 VII BATTERY REPLACEMENT 24 VIII ACCESSORIES 25...

Page 5: ...en using this tester in any cases especially in which the voltage circuit bears the voltage of AC100V or more The tester shall be applied connecting insulating rod with the hand holding on the fifth r...

Page 6: ...hall be used to gently rub down the tester Stop using and mothball then leave it to authorized organization for handling in case that continuing use can cause safety hazard due to the performance of t...

Page 7: ...munication link etc it adopts the wireless transmission signal that is capable of penetrating wall obstacles with a direct line transmission distance of about 30m MEWOI1500D tester is widely applicabl...

Page 8: ...ity moisture proof strong shock resistance bending resistance high insulation high flexibility and so on Monitoring Software Functions such as real time monitoring historical data search accessing bro...

Page 9: ...se sequence and leaker in the three channel high low voltage current transformer and the voltage transformers Power supply HV Detector DC6V alkaline batteries 1 5V AAA 4 Principal machine DC6V alkalin...

Page 10: ...ange of Ratio error 0 0 9 9 the principal machine can sound a alarm of beep beep beep if the measured value is more than the preset error Phase polarity Symbol indicated for in phase positive polarity...

Page 11: ...A displayed Zero signal indication The symbol is shown if the principal machine can t receive the signal from the HV detector Backlight Control Available ON OFF means to open close the backlight Alarm...

Page 12: ...size Outer diameter 32mm inner diameter 24mm 1m piece 5 pieces Lead length of LV current clamp 2 m Piece Dielectric strength AC100kV rms between HV detector cover and the 5 th insulating rod the AC10...

Page 13: ...rations Check if any damage exists for each part before operating the tester it can be put into use only after being qualified Install the battery according to the requirements set forth in the manual...

Page 14: ...respectively and the data measured by LV current clamps of CT1 CT2 and CT3 can be displayed on the position of R S and T on screen respectively the LCD can display the symbol if the principal machine...

Page 15: ...sualty Only when all of the five insulating bars are connected can the high voltage line be detected otherwise there may be the danger of electric shock resulting in personal injury or casualty Danger...

Page 16: ...nd can be shown on R phase If the principal machine shows that the primary circuit current value is OL it is indicated that the primary circuit current exceeds the upper limit of the high voltage dete...

Page 17: ...13 Notice please take the instrument away from the wire after the detection is finished for a safe operation It is available to measure HA current leaker by the tester...

Page 18: ...e 600V or 10A otherwise there can be the danger of electric shock resulting in personal injury or casualty 1 Connect three LV current clamps to the corresponding principal machines power on the machin...

Page 19: ...15 3 Reference Diagram Recording the circuit current monitoring leakers from equipment Detecting cable leakers in wall Detecting leaker from grounding wire...

Page 20: ...ption of battery 5 Test of CT ratio polarity 1st the current detected by single channel HV detector the primary current for CT 2nd the current collected by three channel LV current clamp the secondary...

Page 21: ...benchmark of secondary current in the range from 0 00A to 99 99A CT ratio of transformation based on benchmark of 10kV YY the HV detector collects the secondary current from the busbar 380V of transf...

Page 22: ...row key from the CT ratio display mode to the error test mode For example The pretest current transformer is a low voltage terminal CT of 10kV 380V transformer which primary current is 151 5A and whic...

Page 23: ...ratio display mode and press the MEM key and the Down arrow key to set the basic value for transformation of secondary current while calculate the CT ratio on basis of the new basic value The default...

Page 24: ...25 more than the T phase otherwise it is negative The cursor rotates clockwise on LCD under the positive phase sequence and rotates counterclockwise under negative phase sequence as shown in the figu...

Page 25: ...n is completed The tester can save up to 1 500 sets of data if the memory is full the symbol Full is shown it is necessary to clear the memory for the more storage 10 Data search Press the MEM key to...

Page 26: ...and run the monitoring software if the software displays the serial port is open and connected it is available to access the historical data which can be uploaded to the computer and saved under the...

Page 27: ...he error by the above preset its setting range is from 0000 to 9999 0 0 9 99A Press the Left or Right arrow key to move the cursor press the Up or Down arrow key continuously or interruptedly to chang...

Page 28: ...or interruptedly to change the setting range move the cursor to the OK or Cancel position and press the MEM key to return the previous menu 4 Set backlight Press the Left or Right arrow key to move th...

Page 29: ...ied batteries Paying special attention to the specification and electrode of new batteries close the battery cover tighten the two new screws 3 Press the POWER key to check if the instrument starts up...

Page 30: ......