10.5.3.6.
Characteristics
In the menu window "Characteristic" a user-defined sensor characteristic curve can be defined.
It can be selected as "User defined" in the menu item "Analog inputs", see chapter
in
the pop-up table "Config". The actual value shown there is then interpolated using this table.
In the pop-up menu "Range" the physical quantities voltage, voltage with connected pull-up
resistor, current and resistance linear or exponential are available.
In the input field "Unit" a unit can be entered.
In the input fields "x" and "y" the given value pairs can be edited. Here in the example, the X-
value as a support point for the temperature and the Y-value for the corresponding resistance
value.
Up to 10 value pairs can be defined by activating the action field "Add Node".
By activating the action field with the trashcan symbol, interpolation points can be removed.
The value pairs are only accepted when the action field "Save" is pressed.
10.5.3.7.
Record
In the menu window "Record" stored data of inputs and outputs can be displayed, which have
been configured for an acquisition as described in chapters