7 SG9H 70 en
43
14
CONFIGURATION PARAMETERS
DTM
LUI *)
Screen
Parameter
Values / Range
Parameter
Values / Range
-
-
MODE
AUTO
, MAN
-
-
TUNE
2 …20 (default 5)
Settings
Frame Language
English, Suomi, Deutsch
LANG
ENG
, GER, FRE
Operation Unit
HART Tag
free text (default POS1234)
-
-
Description
free text (default SG9000)
-
-
Device Date
free text (default 02.02.2005)
-
-
Message
free text (default SG9000)
-
-
HART Long Tag
free text (default SG9000)
-
-
Assembly Related
Actuator Type
Double Acting, Single Acting
ATYP
2-A
, 1-A
Valve Acting Type
Rotary, Linear
VTYP
ROT
, LIN
Maximum Valve Speed
Slow, Moderate, Fast
MAXS
FST
, SLO, STD
Dead Angle
0.0 … 50.0 %
A0
0.0
… 99.0 %
Positioner Fail Action Direction
Close, Open
PFA
CLO
, OPE
Position Transmitter Direction
Normal Direction, Reverse, Not In Use
-
-
Signal Modification
Direction
Rising Setpoint to Open, Rising Setpoint to Close
DIR
CLO,
OPE
Setpoint Trigger Level
20.0 … 80.0 % (default 50.0 %)
LEV
20.0 …80.0 %
(default 50.0 %)
SW Limit Switch - Closed Below
0.0 … 100.0 % (default 0.0%)
-
-
SW Limit Switch - Open Above
0.0 … 100.0 % (default 100.0%)
-
-
Stroke Profile Open
Stroke Time
default 10 s
STOP
0
… 999
Stroke Profile Type
Linear, Slow Start, Slow Start and End, Equal Percentage, Quick
Opening
SPOP
1
, 2, 3, 4, 5
Custom Profile
21 parameters, range 0.0 … 100.0
-
-
Stroke Profile Close
Stroke Time
default 10 s
STCL
0
… 999
Stroke Profile Type
Linear, Slow Start, Slow Start and End, Equal Percentage, Quick
Opening
SPCL
1
, 2, 3, 4, 5
Custom Profile
21 parameters, 0.0 … 100.0
-
-
Monitoring Dynamic
Variables
Sampling Rate
1 … 60 s
-
-
Warnings Limit for
Performance
Stroke Time Deviation - Open
0 … n s (default 5 s)
-
-
Stroke Time Deviation - Close
-
-
Spool Valve Reaction Time - Open
0.0 … 60,0 s (default 5 s)
-
-
Spool Valve Reaction Time - Close
-
-
Valve Reaction Time - Open
0.0 … 60,0 s (default 10 s)
-
-
Valve Reaction Time - Close
-
-
Supply Pressure - Low Limit
2.0 … 8.0 bar (default 2.5 bar)
-
-
Supply Pressure - High Limit
2.0 … 8.0 bar (default 7.5 bar)
-
-
Temperature - Low Limit
-40.0 … 85.0 °C (default -35 °C)
-
-
Temperature - High Limit
-40.0 … 85.0 °C (default 80 °C)
-
-
Warning Limits for Counters
Total Operation Time
0 … n h (default 216000 h)
-
-
Total Valve Full Strokes
0 … n (default 2000000)
-
-
Total Actuator Full Strokes
-
-
Alarm Limits
Stroke Time Deviation Open - High Limit
0 … n s (default 5 s)
-
-
Stroke Time Deviation Close - High Limit
-
-
Valve Stuck Deviation -
Position Deviation
0.0 … 100.0 % (default 5.0 %)
-
-
Valve Stuck Deviation - Latch Time
0 … 999 s (default 30.0 s)
-
-
Unallowed Valve Movement -
Latch Time
0 … n s (default 5 s)
-
-
Supply Pressure - Low Limit
1.0 … 10.0 bar (default 2,5 bar)
-
-
Supply Pressure - High Limit
1.0 … 10.0 bar (default 8 bar)
-
-
Supply Pressure - Latch Time
0 … n s (default 30 s)
-
-
Temperature - Low Limit
-40.0 … 85.0 °C (default -35 °C)
-
-
Temperature - High Limit
-40.0 … 85.0 °C (default 80 °C)
-
-
Temperature - Latch Time
0 … n s (default 120 s)
-
-
Spool Valve Reaction Time - High Limit
0 … n s (default 50 s)
-
-
Supply Pressure Fail Action - Low Limit
0.0 … 8.0 bar (default 1.0 bar)
-
-
HART Configuration
1st Dynamic Variable Code
Setpoint, Valve Position, Cylinder Pressure (C1), Cylinder Pressure
(C2), Actuator Pressure Difference, Supply Pressure, Device
Temperature, Target Position
-
-
2nd Dynamic Variable Code
-
-
3rd Dynamic Variable Code
-
-
4th Dynamic Variable Code
-
-
Supply Pressure Unit
bar, psi
-
-
Pressure Difference Unit
-
-
Cylinder Pressure (C1) Unit
-
-
Cylinder Pressure (C2) Unit
-
-
Device Temperature Unit
°C, °F
-
-
Response Preambles
5 … 20
-
-
Burst Mode Command
1, 2, 3, 9
-
-
1st Burst Variable Code
Setpoint, Valve Position, Cylinder Pressure (C1), Cylinder Pressure
(C2), Actuator Pressure Difference, Supply Pressure, Device
Temperature, Target Position
-
-
2nd Burst Variable Code
-
-
3rd Burst Variable Code
-
-
4th Burst Variable Code
-
-
Device HART Address
Multidrop
Disabled, Enabled
-
-
Address
0, 1 … 15
-
-
*) Default values are set in boldface type