continued to within 1 to 2 inches (25 to 50mm) of the transmitter terminals.  The shield itself 

should be connected to the provided shield terminal.  The shield connection should be as 

short as possible.  Ensure that all shields are connected only at one end, preferably at the 

transmitter.  Alternate shield connections are possible such as to instrumentation grounds, 

etc.  In general, connection of shields to earth grounds should be avoided except at one cen

-

tral earth grounding point for a complete system as “ground loops” may be created, which 

can introduce unwanted power frequency pickup.

SENSOR MALFUNCTION 

The signal conditioners are provided with a sensor malfunction detector, which causes the 

output current to drop below 3.5 mA, the SENSOR OK LED to extinguish and the Display 

(5544 & 5545 only) to read zero, in the event of an open circuit.  The 5535 and 5545 also 

detect incorrect polarity or shorted cable conditions.

CALIBRATION

 

NULL OFFSET

The offset calibration can be checked as follows: 

Disconnect the transducer cable leads from the signal conditioner and connect the following 

in its place: 

• 

Model 5534, 5544: Short circuit transducer connections, except for -40X, -50X,   

 

-60X and -70X (piezovelocity) units which require a resistor as specified for Models  

 

5535 & 5545. 

• 

Model 5535, 5545: Tie the transducer connections together as follows:

 

4mA sensor current source conditioners — 2.49K ohm resistor 

 

10mA sensor current source conditioners — 1K ohm resistor 

 

No sensor current source conditioners — short circuit 

To adjust, remove the plastic plug from the Z (Zero) control and adjust the latter to obtain 

exactly 4 mA output. Remove the short (or the resistor) and reconnect the transducer cable. 

SPAN

  

The 20 mA output (SPAN) is factory set to the full scale value indicated on the nameplate 

and is not field adjustable. The most reliable way to check the calibration of the sensor and 

signal conditioner as a system is to compare the indicated vibration with an independent, 

accurate vibration measurement at the same location.

FORMULA:

 

Measured mA - 4 mA 

                   

       20 mA - 4 mA

EXAMPLE:   

 

Measured mA      

Full  Scale  Vib     

Actual Vib

<3.5 

1.0 ips, pk          

Sensor fault

  4.0

1.0 ips, pk            

0.0 ips, pk

12.0

1.0 ips, pk  

0.5 ips, pk

20.0

1.0 ips, pk  

1.0 ips, pk

STARTUP CURRENT

The signal conditioners employ a DC-DC converter.  As with all converters of this nature, a 

large current spike occurs at startup.  The current spike has a peak of 100 mA and lasts for 

40 ms.  Care should be exercised when wiring several units onto one supply.  Power supplies 

without adequate capacity will not allow the units to start properly.  The internal power sup

-

ply  fuse may open as a result of this condition.