Power Network Application Trainer
– Earthing / Grounding network impedance measurement
101
To get total pylon impedance, we need to calculate it from the individual values. Four
legs pylon could be presented as parallel connection of four impedances, so the
calculated object impedance is:
Foot Nm. 1
22,4
Ω
Foot Nm. 2
10,90
Ω
Foot Nm. 3
22,1
Ω
Foot Nm. 4
5,47
Ω
Total impedance
2,74
Ω
Table 24-
2: Pylon foot’s impedance
Measuring pylon resistance with single flex clamp is time consuming measurement;
since for each measurement we need to move flex clamps to the next foot.
To speed up the measurement and skip the manual pylon earth resistance calculation,
we propose to use four flex
– clamp (optional accessories).
4.1.3.2 S
– Flex measuring method by using one Flex-clamp with
simulated broken foot resistance and resistive earthing type
Figure 68-2: S-Flex measurement setup with MI 3290
This exercise presents procedure how to perform complete earth measurement on the
transmission pylon with four foots with only one flex clamp, with the simulation of broken
Summary of Contents for MI 3298
Page 55: ...Power Network Application Trainer Earthing Grounding network impedance measurement 55 ...
Page 56: ...Power Network Application Trainer Earthing Grounding network impedance measurement 56 ...
Page 124: ...Power Network Application Trainer Earthing Grounding network impedance measurement 124 ...
Page 228: ...MI 3290 Earth Analyser 228 ...
Page 229: ...MI 3280 Digital Transformer Analyser 229 ...
Page 230: ...MI 3280 Digital Transformer Analyser 230 ...
Page 231: ...MI 3250 MicroOhm 10A 231 ...
Page 232: ...MI 3205 TeraOhmXA 5kV 232 ...