MI 3102(H) BT
Eurotest
XE
Measurements
36
Figure 5.7: Connection of 2.5 kV test lead (U
N
=2.5 kV)
Insulation resistance measuring procedure
Select the
R ISO
function using the function selector keys.
Set the required
test voltage
.
Enable and set
limit
value (optional).
Disconnect
tested installation from mains supply (and discharge insulation as required).
Connect
test cable to the instrument and to the item to be tested (see
Different test cable must be used for testing with nominal test voltage U
N
≤ 1000 V and
U
N
= 2500 V. Also different test terminals are used.
The standard three-wire test lead, schuko test cable or plug / tip commanders can be
used for the insulation test with nominal test voltages ≤ 1000 V. For the 2500 V
insulation test the two wire 2.5 kV test lead should be used.
Press the
TEST
key to perform the measurement (double click for continuous
measurement and later press to stop the measurement).
After the measurement is finished wait until tested item is fully discharged.
Store
the result by pressing the
MEM
key (optional).
Figure 5.8: Example of insulation resistance measurement result
Displayed results:
R
.............. insulation resistance
Um
........... test voltage (actual value)