MI 3155
Eurotest
XD
Test and measurements
155
7.24
Harmonics
Figure 7.83: Harmonics menu
Measurement parameters / limits
Ch1 clamp type
Current clamp adapter
[A1018, A1019, A1391]
Range
Range for selected current clamp adapter
A1018 [20 A]
A1019 [20 A]
A1391 [40 A, 300 A]
Limit(THDu)
Max. THD of voltage
[3 % ... 10 %]
Connection diagram
Figure 7.84: Harmonics measurement
Measurement procedure
Enter the
Harmonics
function.
Set parameters / limits.
Connect 3-wire test lead and current clamp to the instrument.
Connect 3-wire test lead and current clamp to the item to be tested, see
Start the continuous measurement.
Stop the measurement.
Save results (optional).