0800 111 780
www.portableappliancetesters.co.nz
Extension Leads
1.
Connect the
IEC LEAD
(supplied with the
DeltaPAT) into the socket labelled ‘IEC’ on
the top left of the DeltaPAT.
2.
Plug the
Extension Lead
into the front of
the DeltaPAT and the other in the IEC LEAD
(above) to create a circuit.
3. On the DeltaPAT
Main Menu,
select
SIMPLE
TEST
and press
TEST
.
4. Using the arrow keys scroll to
IEC
.
5. Press the
TEST
button to start the test.
6. The DeltaPAT will cycle through the ‘Earth
Bond’, ‘Insulation Resistance Test’ and
‘Polarity Test’.
7.
A
PASS
or
FAIL
will be indicated on the
screen once the tester has been completed.
8. Press the
ESC
to start a new test.
Leakage Current
1. Testing Leakge Current on Class I, Class II
and RCD’s - refer to the above procedures.
However, ensure that the ‘
MAINS
’ supply is
connected and the correct test is selected
on
SIMPLE TEST
mode and
LKG
is selected.
RCD Testing
1. Ensure that the
MAINS
supply is connected
to 230V using an IEC cable supplied.
2. Plug the RCD to the front of the DeltaPAT.
3. Connect the other
IEC Lead
(supplied with
the DeltaPAT) into the socket labelled ‘IEC’
on the top left of the DeltaPAT and the
other end into a socket of the RCD under
test.
4. On the DeltaPAT
Main Menu,
select
SINGLE
TEST
and press
TEST
.
5. Using the arrow keys scroll to
RCD
and
press
TEST
.
6. Using the arrow keys select
Out: PRCD
(portable RCD).
7. Press the ‘TAB’ button and select
1Δ: 30mA
or 10mA.
8. Press the ‘TAB’ button and select
Mod:
AUT).
9. Press the
TEST
button to start the test.