
Quick installation manual REV:201706
BREAK-xDW-S-4C
Digital optoconverters RS485, RS422 and contact
www.metel.eu
www.metel.eu
www.metel.eu
www.metel.eu
6/6
Installation and Settings
1. Mounting
Mount the converter to flat surface or DIN35 rail.
2. Connect supply
10-30VAC or 10-60VDC acc. to the picture below. The supply
is indicated by yellow power LED PWR.
3. Connect optical fibers
terminated by SC connector (grinding PC). After
interconnection of TDW-S-4C and RDW-S-4C LED LOCK
switches
off.
4. Connect signal wires
according to the pictures below.
Connect RS485 buses to A+ and B- terminals.
For RS422 transmission use e.g. BUS1 for reception and BUS2
for transmission on one side; the other side will then use
BUS1 for transmission and BUS2 for reception.
Terminate the data buses with 120
Ω
resistance by switching
the DIP switch to ON position.
Connect shielding to only one side to the GND terminal.
5. Connect inputs and relay outputs
IN
- digital inputs can be activated by
connection with GND or by low level of TTL.
OUT
- relay outputs
max. load 125VAC/0.5A or 60VDC/0.3A
Contacts are closed after input activation.
RELAY LOCK - relay reacting to error conditions. Used for
alarm systems, starting of back-up, etc. The
function is described in the picture below.
6. Indications
LED PWR - by switching on detects supply
LED LOCK - by switching on detects relay closure
- by switching on detects optics interruption
- by switching on detects failure of a remote
device
BUS1,2 Rx/Tx
- green LED Tx blinking
–
data transmission
- red LED Rx blinking
–
data reception
RELAY
max. 125VAC/0.5A
or 60VDC/0.3A
WHEN IS
- LOCAL DEVICE IN DE-ENERGIZED STATE
- REMOTE DEVICE IS IN FAILURE
- OPTICS IS CORRUPTED
COM
AND
NC
ARE CONNECTED.
WHEN IS
- LOCAL DEVICE IS POWERED
- REMOTE DEVICE IS WORKING
- OPTICS IS OK
COM
AND
NO
ARE CONNECTED.
TDW-S-4C
Tx - 1310nm
Rx - 1550nm
RDW-S-4C
Tx - 1550nm
Rx - 1310nm
BUS TERMINATION, ON = 120
Ω
PWR/LOCK
IN OUT
IN
B
U
S
1
B
U
S
2
120R BUS1
120R BUS2
LO
C
K
TYPE: T DW-S-4C-BOX
TYPE: RDW-S-4C-BOX
CODE: 1-505-220
CODE: 1-605-220
1x INPUT
2x RS485
RS422
Rx
Tx
polytron
1x RELAY OUT
GND
N.O.
COM
Rx1/Tx1 | Rx2/Tx2
+A
-B
GND
+A
-B
N.O.
COM
N.C.
SU PPLY
10-30VAC
10-60VDC
RELAY
SUPPLY
10-30VAC
10-60VDC