Installation and Settings 

1. Mounting

Mount the converter to flat surface or DIN35 rail.

 

2. Connect supply 

10-30VAC or 10-60VDC acc. to the picture  below. The supply 
is indicated by yellow power LED PWR. 

3. Connect optical fibers

terminated by SC connector (grinding PC). After 
interconnection of  TDW-S-4C and RDW-S-4C LED LOCK 
switches

 

off.

4. Connect signal wires

according to the pictures below.
Connect RS485 buses to A+ and B- terminals. 
For RS422 transmission use e.g. BUS1 for reception and BUS2 
for transmission on one side; the other side will then use 
BUS1 for transmission and BUS2 for reception.
Terminate the data buses with 120

Ω

 resistance by switching 

the DIP switch to ON position.
Connect shielding to only one side to the GND terminal.

5.  Connect inputs and relay outputs

IN   

  -  digital inputs can be activated by 
connection with GND or by low level of TTL.

OUT

  -  relay outputs 
max. load 125VAC/0.5A or 60VDC/0.3A
Contacts are closed after input activation.

RELAY LOCK -  relay reacting to error conditions. Used for 

alarm systems, starting of back-up, etc. The 
function is described in the picture below.

6.  Indications

LED PWR  - by switching on detects supply
LED LOCK  - by switching on detects relay closure

- by switching on detects optics interruption
- by switching on detects failure of a remote 
device

BUS1,2 Rx/Tx

- green LED Tx blinking 

– 

data transmission

- red LED Rx blinking 

– 

data reception

RELAY 
max. 125VAC/0.5A
or 60VDC/0.3A

WHEN IS 
- LOCAL DEVICE IN DE-ENERGIZED STATE
- REMOTE DEVICE IS IN FAILURE
- OPTICS IS CORRUPTED 

COM 

AND 

NC

 ARE CONNECTED.

WHEN IS 
- LOCAL DEVICE IS POWERED
- REMOTE DEVICE IS WORKING
- OPTICS IS OK

COM 

AND 

NO

 ARE CONNECTED.

TDW-S-4C
Tx - 1310nm 
Rx - 1550nm

RDW-S-4C
Tx - 1550nm 
Rx - 1310nm

BUS TERMINATION, ON = 120

Ω

PWR/LOCK

IN   OUT

IN

B

U

S

1

B

U

S

2

120R BUS1

120R BUS2

LO

C

K

TYPE:  T DW-S-4C-BOX
TYPE:  RDW-S-4C-BOX

CODE: 1-505-220
CODE: 1-605-220

1x INPUT

2x RS485

RS422

Rx

Tx

polytron

1x RELAY OUT

GND

N.O.

COM

Rx1/Tx1 | Rx2/Tx2

+A

-B

GND

+A

-B

N.O.

COM

N.C.

SU PPLY

10-30VAC

10-60VDC

RELAY

SUPPLY
10-30VAC
10-60VDC

Reviews: