Metel 1-759-226 Installation Manual Download Page 6

www.metel.eu

6/10

Installation manual REV:201301

2G(200M)-2.1.4.E PoE++

LAN-RING System PoE++ Managed Switches

Activation PoE/PoE++ on Fast Ethernet ports

1. In menu 

„Ports“

 select FE ports  FE (

„P1 – P4“

),

     where you want to activate PoE supply.
2. Checking the „

Enabled"

 to enable PoE power supply

     on the port.
3. On one of the ports „

P1 - P4

" You can turn

     PoE + + by checking the „

Poe + + Enabled

".

Note: Item 

„Ignore discovery“

 - pernamently turn on 

PoE power supply without detection and classification 
of PoE end devices.

The setting consists of the following steps:

1. In menu

 „Bus/Mode“

 set the system you are using. If not provided select “

RS485

”  set „

Speed

“ and „

Data bits

“. If the system 

is provided in the menu no further setting in menu 

„Bus“ 

is needed. The switch sets it automatically.

2. In menu 

„Ethernet“

 set receiving and transmitting addresses in range 239.0.0.0 - 239.255.255.255 (multicast). 

topology BUS – set the same receiving and transmitting  address on all switches.
topology POINT-to-POINT – set the addresses “crosswise”:

Example:  Device 1

receiving address - 239.192.168.2, transmitting address 1 - 239.192.168.3

Device 2

receiving address - 239.192.168.3, transmitting address 1 - 239.192.168.2

LAN-RING

Tx 239.192.168.1

Rx 239.192.168.1

Tx 239.192.168.1

Rx 239.192.168.1

Tx 239.192.168.1

Rx 239.192.168.1

Fast Ethernet

LEGEND

RS485

Gigabit

1x MM or SM fiber

Setting of RS485 transmission in UDP mode (multicast)

Summary of Contents for 1-759-226

Page 1: ...MM or SM fiber Fast Ethernet LEGEND others Gigabit Ethernet supply with PoE 48 56VDC without PoE 10 60VDC 10 30VAC holder DIN35 LOCK for mounting to DIN35 included Ring topology LAN RING Overvoltage p...

Page 2: ...s The optimum placement of the switch devices and cables connected to the switch is in protection area of a lightning rod i e ZBO0B zone acc to IEC 62305 4 The switches ports are protected in two ways...

Page 3: ...Opening closing of one or more inputs on other switches and I O modules Function IP watchdog that automatically restarts frozen devices SNMP protocol from integration software e g C4 Everything is adj...

Page 4: ...s Auto negotiation Auto MDI MDI X and Power down The ports also support supplying of terminal devices over Cat 5e cable acc to IEEE 802 3 af IEEE 802 3at max 15 4W per port 1x Fast Ethernet port with...

Page 5: ...and optic fiber interruption In non alarm state COM and N C are closed IN OUT digital inputs are activated by closing to GND or by TTL level 0 0 3V log 0 and 2 7V 5V log 1 TTL outputs can be mapped i...

Page 6: ...not provided select RS485 set Speed and Data bits If the system is provided in the menu no further setting in menu Bus is needed The switch sets it automatically 2 In menu Ethernet set receiving and...

Page 7: ...you are using If not provided select RS485 set Speed and Data bits If the system is provided in the menu no further setting in menu Bus is needed The switch sets it automatically 2 In menu Ethernet T...

Page 8: ...kbps overvoltage protection 30A 8 20us PoE indication POx PoE ON FAx PoE fault P P4 Ethernet 10 100 BASE T PoE ports LED DUPLEX COLLISION ACT LED ACTIVITY overvoltage protection 1000A 8 20us LAN RING...

Page 9: ...1490nm CD connected fiber detection ACT activity detection P5 gigabit Ethernet 10 100 1000 BASE T overvoltage protection 30A 8 20us USB local management application SIMULand over USB A B cable P R LED...

Page 10: ...www metel eu 10 10 Installation manual REV 201301 2G 200M 2 1 4 E PoE LAN RING System PoE Managed Switches Size 2G a 200M 2 1 4 E PoE...

Reviews: