Operation
GUPS 2400A
–104 Operation Manual
3-9
3.9.4.2
Display Calibration Values
Enter a command ‗k‘ (lowercase K) character to display the calibration constants for the A/D
converter algorithms values. For example:
Calibration Constants:
80 percent current: 32F8
// Output current in hexadecimal
105 percent current: 424B
150 percent current: 50E7
Minimum voltage band: 2000
// Output voltage in hexadecimal
Maximum voltage band: 2100
Battery 200 volts 0198
// Battery voltage in hexadecimal
Battery bad: 0240
Battery shutdown: 0268
AC line A-B scale factor: 31030
// AC input line voltage scale factors in decimal
AC line B-C scale factor: 31030
AC line C-A scale factor: 31030
Vout rdbk cal: 91.3
/
/ Output voltage readback calibration in
Vout rdbk dvm: 114.5
floating point format
3.9.4.3
Display Status Registers and A/D Values
Enter a command ‗s‘ (lowercase S) character to display the two 16-bit status registers, along
with the A/D values of the AC input voltage, Output voltage, Output current, and Battery/Charger
voltage. For example:
Status word 1: 5540
// 16-bit status flags in hexadecimal
Status word 2: 0283
A/D Values:
// A/D values in floating point and hexadecimal
Output Voltage: 115.0
2314
Output Current: 3.25
0028
Input Voltage A-B: 200.0
4E20
Input Voltage B-C: 200.0
4E20
Input Voltage C-A: 200.0
4E20
Battery Voltage: 190.00
0284
The status word formats are explained in Section 3.9.6.
3.9.4.4
Display Firmware Version Number
Enter a command ‗v‘ (lowercase V) character to display the version number of the firmware.
For example:
Firmware version number: P/N 5152457-01, Rev 2.0