Metal Samples MS2701E Operator'S Manual Download Page 13

11

 

 

i.

 

Baud

 

Rate

 

and

 

Default

 

Communication

 

Parameters

 

 

The

 

default

 

communication

 

parameters

 

for

 

the

 

MS2701E

 

transmitter

 

are

 

provided

 

in

 

Table

 

4

 

below.

  

If

 

necessary,

 

the

 

baud

 

rate

 

can

 

be

 

changed

 

using

 

Positions

 

1

 

and

 

2

 

of

 

Switch

 

2,

 

as

 

illustrated

 

in

 

Table

 

3.

   

 

Parameter

 

Value

 

Baud

 

Rate

 

19200

 

Data

 

Bits

 

8

 

Parity

 

Even

 

Stop

 

Bits

 

1

 

 

Table

 

4.

  

Default

 

Communication

 

Parameters

 

 

ii.

 

Device

 

Address

 

 

Up

 

to

 

32

 

MS2701E

 

transmitters

 

may

 

be

 

connected

 

in

 

a

 

multi

drop

 

network

 

(“daisy

chained”)

 

using

 

a

 

single

 

cable

 

run.

  

However,

 

each

 

transmitter

 

must

 

be

 

set

 

to

 

a

 

unique

 

device

 

address

 

to

 

avoid

 

conflicts.

  

This

 

is

 

done

 

using

 

Positions

 

3

 

through

 

7

 

of

 

Switch

 

2,

 

as

 

illustrated

 

in

 

Table

 

3.

 

 

CAUTION:

  

Be

 

sure

 

to

 

observe

 

the

 

appropriate

 

gas

 

group

 

rating

 

listed

 

on

 

page

 

3

 

for

 

stand

alone

 

or

 

multi

drop

 

operation.

 

 

 

iii.

 

Communication

 

Protocols

 

 

The

 

MS2701E

 

transmitter

 

offers

 

user

selectable

 

RTU

 

or

 

ASCII

 

communication

 

protocols,

 

giving

 

the

 

unit

 

a

 

broader

 

range

 

of

 

compatibility.

  

The

 

communication

 

protocol

 

is

 

set

 

using

 

Position

 

8

 

of

 

Switch

 

2,

 

as

 

illustrated

 

in

 

Table

 

3.

 

 

iv.

 

Termination

 

Resistor

 

 

To

 

ensure

 

proper

 

operation,

 

the

 

RS

485

 

network

 

must

 

be

 

terminated

 

properly

 

with

 

a

 

termination

 

resistor.

  

To

 

facilitate

 

this,

 

each

 

MS2701E

 

transmitter

 

has

 

a

 

built

in

 

120

 

termination

 

resistor

 

that

 

can

 

be

 

switched

 

on

 

or

 

off

 

using

 

Position

 

10

 

of

 

Switch

 

2.

  

Once

 

all

 

units

 

have

 

been

 

installed,

 

be

 

sure

 

to

 

enable

 

the

 

termination

 

resistor

 

of

 

the

 

last

 

unit

 

in

 

the

 

network.

  

The

 

termination

 

resistors

 

of

 

all

 

other

 

transmitters

 

should

 

be

 

turned

 

off.

 

v.

 

Data

 

Registers

 

 

Table

 

5

 

lists

 

the

 

data

 

registers

 

of

 

the

 

MS2701E

 

transmitter.

 

 

No

 

Register

 

Address

 

Description

 

1

 

40001

 

Device

 

Status

 

2

 

40002

 

Device

 

Address

 

3

 

40003

 

Baud

 

Rate

 

4

 

40024

 

DAC

 

Value

 

5

 

40026

 

Probe

 

Switch

 

Setting

 

 

Table

 

5.

  

Modbus

 

Data

 

Registers

 

Summary of Contents for MS2701E

Page 1: ...S 485 Transmitter Operator s Manual Metal Samples Company A Division of Alabama Specialty Products Inc 152 Metal Samples Rd Munford AL 36268 Phone 256 358 4202 Fax 256 358 4515 E mail msc alspi com In...

Page 2: ...n Parameters 11 ii Device Address 11 iii Communication Protocols 11 iv Termination Resistor 11 v Data Registers 11 c Calibration and Testing 12 i Calibration 12 ii Testing output zero and span 12 iii...

Page 3: ...t in close proximity to the ER probe It is then connected to the probe via a short probe cable See pages 5 and 6 for mounting diagrams and specifications B Principles of Operation The MS2701E transmit...

Page 4: ...ansmitter can measure metal loss amounts as small as 0 0015 of the probe life Metal loss readings taken by the MS2701E transmitter are output as a digital RS 485 signal which can be fed into a plant c...

Page 5: ...60079 0 60079 11 61010 1 CAN CSA Std E66079 0 60079 11 CAN CSA C22 2 No 61010 1 For Stand Alone Use For Multi Drop Use Class I Zone 1 AEx ia d IIC T4 Gb Class I Zone 1 AEx ia d IIB T4 Gb Zone 20 AEx...

Page 6: ...trical Connection 3 Setup and Programming 1 Physical Mounting and Probe Connection When selecting a location to mount the MS2701E transmitter it is important to consider the surrounding environment To...

Page 7: ...for foreign material in the female sockets of the transmitter connector Gently straighten any bent pins and clear any foreign material that may be found Figure 2 Direct Mount Installation b Remote Mou...

Page 8: ...the main PCB via the terminal blocks J2 and J9 as shown in Figure 6 NOTE Do not connect cable shielding to the Transmitter The shield must remain floating at the Transmitter The RS 485 protocol allows...

Page 9: ...arameters shown below The pre approved equipment must be certified to the electrical safety standards for equipment in ordinary locations for example EN IEC CSA UL 61010 1 or EN IEC CSA UL 60950 1 Fai...

Page 10: ...is the most practical method of protecting the MS2701E transmitter when it is installed in a hazardous area In the MS2701E transmitter electrical energy limits are maintained by the use of appropriate...

Page 11: ...gs for each probe type and the various test modes Figure 6 Connector and Switch Details Switch 1 Setting Position 1 2 3 4 Operating Positions Wire Loop Off On On Off Tube Loop Flush On Off On Off Cyli...

Page 12: ...1 2 7 Off On On Off Off 2400 On On 8 On On On Off Off 4800 Off On 9 Off Off Off On Off 9600 On Off 10 On Off Off On Off 19200 Off Off 11 Off On Off On Off 12 On On Off On Off Communication Protocol P...

Page 13: ...ration iii Communication Protocols The MS2701E transmitter offers user selectable RTU or ASCII communication protocols giving the unit a broader range of compatibility The communication protocol is se...

Page 14: ...op type probe at a fixed value To test the unit with the Meter Prover 1 Disconnect power 2 Disconnect the MS2701E transmitter from the probe or if the unit is remote mounted disconnect the probe exten...

Page 15: ...al Samples probe tag as the Multiplier Figure 7 Metal Samples Probe Tag Figure 8 illustrates the relationship between the digital output and Metal Loss In this example a probe with a 10 mil life is as...

Page 16: ...that is too long may give results that are insensitive to system upsets The ideal time period depends on many factors and will vary from system to system It may take some trial and error to settle on...

Page 17: ...transmitter C Maintenance Once installed the MS2701E transmitter requires little maintenance However itisimportanttoverifythe followingitemsperiodicallytoensurecontinuedsafeoperation CAUTION Before p...

Page 18: ...for the probe being used Confirm the probe type and refer to Table 2 on page 9 to verify the appropriate switch settings 3 Perform a visual inspection of the circuit boards to look for any signs of m...

Page 19: ...nd our control B Obtaining Service and Returning the Instrument for Repair If you experience problems with your instrument please contact the factory at 256 358 4202 and ask for customer support for i...

Page 20: ...wn Contact Information for Repair Contact Name Company Phone Number E mail Address Return Shipping Information Recipient Name Company Return Address If different than above Reason for Return Provide a...

Page 21: ...19 Appendix A Drawings A Wiring Diagrams Control Drawing Hazardous Area Wiring Diagram Safe Area Wiring Diagram...

Page 22: ......

Page 23: ...ANCE L O THAT CAN BE CONNECTED BETWEEN RS 485 TERMINALS J9 AND PROBE TERMINALS CN2 IS 0 14mH D D MS2701E MS2801E 2 D D 2 1 2 1 3 S1 J2 J9 S2 D D RS 485 SIGNAL INTERFACE PC PLC DCS HAZARDOUS AREA SAFE...

Page 24: ......

Page 25: ...i Drop operation Revised hazardous area installation control drawing and safe area installation drawing B 2 4 15 Revised entity parameters and hazardous area installation control drawings C 3 2 15 Rev...

Reviews: