GENERAL NOTES:

1.  No dampers/ductless grilles (returns) shall be located in adjacent 24” x 48” ceiling grid modules.
2.  If flexible duct is used, it shall be fastened to the diffuser neck with a steel clamp or #16 S.W.G. (min) galvanized steel wire.

 

 

The flexible  air  duct  shall  be  Class  O  or  Class  I  type,  bearing  the  UL  Listing  Mark-See  the  UL  “Gas  and  Oil  Equipment

 

 

Directory”. Maximum Length of flexible duct shall not exceed 14’–0” in length. The flexible air duct shall not rest on the back

 

 

surface of the ceiling grid or panels and provide a minimum of 4” clearance. The flexible air duct shall not interfere with the closing

 

 

of the MSCD damper.

3.  MSCD Damper/TB5000 Thermal Insulation/Air Diffuser Assemblies are for use in lieu of the hinged-blade, sheet metal damper

 

 

in steel ducts as specified in the individual floor and roof-ceiling design(s) being used, as illustrated and described in the current

 

 

UL Fire Resistance Directory.

4.  If damper has an adjustable volume control, the 2 fuse links (shipped loose with damper) must be installed on damper for proper

 

 

operation.

5.  Cycle damper after installation.

Litho in U.S.A.

©

2011 Metal-Fab, Inc.   Form No. L1801 - 11/11

 

   