Appendix B:
"RGS EI(1) 30 - EI(2) 60 - EW 240 -
Maintenance Instructions
"
1.
□ Identify the door by means of a type of identification
2.
□ Start with an overall visual inspection
3.
□ Close the door completely
4.
□ Carry out the overall visual check again
5.
□ Disconnect the control unit from the mains supply
6.
□ Checking that all fasteners/points are present/used and that they are secure
7.
□ Check rails for damage and/or wear
8.
□ Check panels and wire ropes for damage and/or wear
9.
□ Check that the armor is still properly aligned in the rails (the space between the outside
panel and inside rails should be equal on the left and right)
10.
□ Checking chain transmission for chain tension, wear and alignment
11.
□ Check that the limit switches are still correctly adjusted;
-
□ Top position: underside of armor maximum equal to day height
-
□ Bottom position: panels stacked (door leaf must not hang on the flame hook)
-
□ Overclose adjustment: check that the door closes properly and that the flame hook
drops into the wall hook
12.
□ Check safety components for proper operation
13.
□ Control of closure at fire alarm
14.
□ Check electrical cabling for damage and fastening
15.
□ Check the batteries in the control unit for function and delivery date, they should be no
more than 2 years old (ambient temperature may shorten service life)
16.
□ Checking that the bearings, adjusting rings and gears are secured
17.
□ Check electrical closing time measurement, note in logbook
18.
□ Check for gravitational closure, plus time measurement, record in logbook
19.
□ Read out cycles/movements in control box, note in logbook
20.
□ Record performed actions, observations, and replaced parts in the logbook
21.
□ Check if the documents are present at the door
Periodic replacement of the following components is necessary for the continued proper
functioning of the door with the declared performance give;
Lowered batter
Standard / highlift
hardware
Vertical hardware
Replaced after;
cycles
year
cycles
year
cycles
year
Palusol
25000
20
25000
20
25000
20
Rubber liquid barrier
1000
3
1000
3
1000
3