Table 1 – Performance and Specifi cation Data – Separated Combustion Propeller Unit heater
Capacity
(MBH)
100 125 150 175 200 225 250 300 350 400
PERFORMANCE DATA ‡
Input
BTU/Hr
100,000 125,000 150,000 175,000 200,000 225,000 250,000 300,000 350,000 400,000
(kW)
(29.3)
(36.6)
(43.9)
(51.2)
(58.6)
(65.9)
(73.2)
(87.8)
(102.5)
(117.1)
Output
BTU/Hr
80,000 100,000 120,000 140,000 160,000 180,000 200,000 240,000 280,000 320,000
(kW)
(23.4)
(29.3)
(35.1)
(41.0)
(46.9)
(52.7)
(58.6)
(70.3)
(82.0)
(93.7)
Thermal
Effi
ciency
(%)
80 80 80 80 80 80 80 80 80 80
Free
Air
Delivery
CFM
1,480 1,650 2200 2,530 2,640 2,700 3,100 4,400 5,000 5,300
(cu. m/s)
(0.699)
(0.779)
(1.038)
(1.194)
(1.246)
(1.274)
(1.463)
(2.077)
(2.360)
(2.502)
Air
Temperature
Rise
°F
50 56 50 51 56 61 60 50 52 56
(°C)
(10)
(13)
(10)
(11)
(13)
(16)
(16)
(10)
(11)
(13)
Outlet Velocity FPM
775
910
1045
1070
1000
950
980
1100
1150
1050
(m/s)
(3.9)
(4.6)
(5.3)
(5.4)
(5.1)
(4.8)
(5.0)
(5.6)
(5.8)
(5.3)
Full
Load
Amps
at
115V
(ODP)
4.5 6.1 6.6 7.7 7.7 7.7 7.7 11.3
13.5 13.5
MOTOR DATA:
Motor
HP 1/20
1/10 1/4 1/3 1/3 1/3 1/2 (2)1/4
(2)1/3
(2)1/3
Motor
(kW)
(0.037) (0.075) (0.186) (0.249) (0.249) (0.249) (0.373) (0.186) (0.249) (0.249)
Motor
Type
(ODP)
SP SP PSC PSC PSC PSC PSC PSC PSC PSC
RPM
1,050 1,050 1,140 1,140 1,140 1,140 1,140 1,140 1,140 1,140
Amps
@
115V
(ODP)
2.6 4.2 4.7 5.8 5.8 5.8 5.8 9.4
11.6 11.6
DIMENSIONAL DATA Inches (mm)
“A” Height to Top of Unit
31-1/4
31-1/4
36-1/4
36-1/4
36-1/4
36-1/4
36-1/4
36-1/4
36-1/4
36-1/4
(794)
(794)
(921)
(921)
(921)
(921)
(921)
(921)
(921)
(921)
“B” Height to Top of Hanger
34-1/16
34-1/16
39-1/16
39-1/16
39-1/16
39-1/16
39-1/16
39-1/16
39-1/16
39-1/16
(865)
(865)
(992)
(992)
(992)
(992)
(992)
(992)
(992)
(992)
“C” Hanging Distance Width
14-3/4
17-1/2
17-1/2
20-1/4
23
25-3/4
28-1/2
34
39-1/2
45
(375)
(445)
(445)
(514)
(584)
(654)
(724)
(864)
(1003)
(1143)
“D”
Discharge
Opening
Width
15-3/8 18-1/8 18-1/8 20-7/8 23-5/8 26-3/8 29-1/8 34-5/8 40-1/8 45-5/8
(391)
(460)
(460)
(530)
(600)
(670)
(740)
(879)
(1019)
(1159)
“E”
Width
of
Unit
17-7/8 20-5/8 20-5/8 23-3/8 26-1/8 28-7/8 31-5/8 37-1/8 42-5/8 48-1/8
(454)
(524)
(524)
(594)
(664)
(733)
(803)
(943)
(1083)
(1222)
“F” to Centerline of Flue
5-7/8
7-1/4
7-1/4
8-5/8
10
11-1/4
12-3/4
15-1/2
18-1/4
21
(149)
(184)
(184)
(219)
(254)
(286)
(324)
(394)
(464)
(533)
Flue
Size
Diameter
Inches** 4 4 4 4 5 5 5 6 6 6
(Diameter mm)
(102)
(102)
(102)
(102)
(127)
(127)
(127)
(152)
(152)
(152)
Air
Inlet
Size-Inches
4 4 4 4 5 5 5 6 6 6
(mm)
(102)
(102)
(102)
(102)
(127)
(127)
(127)
(152)
(152)
(152)
Fan
Diameter-Inches
14 16 16 18 18 18 18 16 18 18
Gas
Inlet-Natural
Gas-Inches 1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4
Gas
Inlet-LP
Gas-Inches
1/2 1/2 1/2 1/2 1/2
←
1/2 or 3/4
→
Approx.
Shipping
Wt.
lb.
200 228 256 284 312 340 368 432 488 545
(kg)
(91)
(103)
(116)
(129)
(142)
(154)
(167)
(196)
(221)
(247)
4
DIMENSIONS .XXX STANDARD UNITS
DIMENSIONS IN PARENTHESIS (XXX) MILLIMETERS
Figure 1A
‡ Ratings shown are for unit installations at elevations between 0 and 2,000 ft. (0 to 610m). For unit installations in U.S.A. above 2,000 ft. (610m), the unit input must be derated 4% for each 1,000 ft.
(305m) above sea level; refer to local codes, or in absence of local codes, refer to the latest edition of the National Fuel Gas Code, ANSI Standard Z223.1 (N.F.P.A. No. 54).
For installations in Canada, any reference to deration at altitudes in excess of 2,000 ft. (610m) are to be ignored. At altitudes of 2,000 ft. to 4,500 ft. (610 to 1372m), the unit must be derated to 90%
of the normal altitude rating, and be so marked in accordance with the ETL certifi cation.
LEGEND: SP = SHADED POLE PSC = PERMANENT SPLIT CAPACITOR ODP = OPEN DRIP PROOF