Mestek Alton Manual Download Page 5

– 5 –

D. Electrical Connections

WARNING: Open all disconnect switches and 

secure in that position before wiring unit. 

Failure to do so may result in personal injury or 

death from electrical shock.

WARNING: Controls  must be protected from 

water. Do not allow water to drip on the ignition 

system.

NOTE: Before installing any wiring, check the unit 

rating plate for supply power rating.

All electrical connections must conform to the current 

edition of: ANSI/NFPA No. 70 National Electrical Code 

and applicable state and local codes.

Entry location for all field-installed and control wiring is 

through the control panel.

If optional disconnect is not furnished with the unit, the 

field provided disconnect must be of the proper size 

and voltage. Refer to unit rating plate for minimum 

circuit ampacity and voltage. The disconnect must be 

installed in accordance with Article 430 of the current 

edition of ANSI/NFPA No. 70 National Electrical Code.

Check the supply voltage before energizing the unit. 

The maximum voltage variation should not exceed  

± 10%. 

NOTE: Should any original wire supplied with the 

unit have to be replaced, it must be replaced with 

wiring material having a temperature rating of at 

least 105° C.

E. Field Piping

CAUTION: To prevent water damage to building 

and equipment piping, drain and vent plugs must 

be installed. 

NOTE: All field-installed piping must conform to 

applicable codes.

Water Piping

All water piping must be in accordance with project 

specifications and the requirements outlined in any ap-

plicable local, state, and national codes. 

Insert a manual shut-off valve in the water supply line 

required for the unit’s direct evaporative section. Com-

plete the piping to each section’s 3/8" make-up water 

inlet.

NOTE: Soft water equipment should not be 

attached to water lines going  to the evaporative 

cooler. "Soft Water" will cause corrosion and 

decrease the effective life of the cooler.

Proper water quality and environmental conditions will 

give you long service life from your direct evaporative 

cooling unit. Significant deviation from “normal” conditions 

may have a bearing on longevity of the equipment.

“Normal” circulating water chemistry falls within the follow-

ing limits:

•  pH between 6.5 and 8.0.

•  Chlorides (expressed as NaCl) below 750 ppm.

•  Calcium (expressed as CaCO

3

) below 1200 ppm - 

except in arid climates where the critical level for scale 

formation may be much lower.

•  Sulfates below 5,000 ppm – if calcium exceeds 1200 

ppm, sulfates should be limited to 800 ppm (less in 

arid climates) to prevent scale formation.

•  Sulfides below 1 ppm.

•  Silica (expressed as SiO

2

) below 150 ppm.

•  Iron below 3 ppm.

•  Manganese below 0.1 ppm.

•  No organic solvents.

•  No organic nutrients which could promote growth of 

algae or slime.

•  Chlorine (from water treatment) below 1 ppm free 

residual for intermittent treatment, below 0.4 ppm free 

residual for continuous chloration.

Insert a manual shut-off valve in the drain line from each 

unit’s direct evaporative section’s drain. 

NOTE: The direct evaporative section of every module 

is provided with an adjustable bleed valve that is 

plumbed to each section’s overflow stand pipe. 

System drainage for the constant water bleed from 

each evaporative section must be provided. 

If units are provided with optional freeze protection and 

automatic drain down kit, install the solenoid valves in the 

following manner:

1.  Install the normally closed and, if provided, the 1/2" or 

3/8” normally open water fill line drain solenoid valve in 

the water supply line at a point not subject to freezing 

temperatures and complete the piping to the make-up 

water inlet connection provided on each unit.

Summary of Contents for Alton

Page 1: ...this appliance is hazardous FOR YOUR SAFETY If you smell gas 1 Open Windows 2 Don t touch electrical switches 3 Extinguish any open flame 4 Immediately call your gas supplier WARNING Improper install...

Page 2: ...s filed They will give you disposition instructions Packing We comply with the packing requirements of the transportation companies and your bill of lading proved that everything was in good condition...

Page 3: ...or to beginning installation of a module that has been in storage for weeks or months the module and its components should be closely inspected Shipments are made F O B Dallas Texas by flat bed truck...

Page 4: ...electrical connections must conform to the current edition of ANSI NFPA No 70 National Electrical Code and applicable local codes The following recommen dations are not intended to supplant any requi...

Page 5: ...ke up water inlet NOTE Soft water equipment should not be attached to water lines going to the evaporative cooler Soft Water will cause corrosion and decrease the effective life of the cooler Proper w...

Page 6: ...the power lines to the line side of the main disconnect switch 2 Mount and wire remote control panel thermostats temperature sensors and any other field installed con trols as indicated on the unit co...

Page 7: ...ntrol inspection However these settings should be verified at the job site 11 Depending on local water pressure a pressure regulating valve may be required to stabilize the make up water flow and the...

Page 8: ...p The bleed off required is dependent on the qual ity of water used and the rate of evaporation As climate conditions change the rate of evaporation may increase thereby requiring an increase in the b...

Page 9: ...ive media damaged or partially blocked 2 Media water distribution header or orifices plugged 1 Localized media face velocity exceeding 500 FPM 2 Evaporative media is damaged 3 Too much recirculating w...

Page 10: ...f rate is excessive 2 Verify that water level in direct evaporative section s sump is correct 3 Direct evaporative section s sump water fill and level control valve defective 1 Minimum bleed off rate...

Page 11: ...or death Periodic maintenance is essential to the efficient operation and extended service life of this equipment Failure to provide maintenance as recommended may void the equipment warranty A Maint...

Page 12: ...ered MODEL NUMBER SERIAL NUMBER FACTORY ORDER F O and PART NUMBERS are required Contact the Technical Services Department at 214 638 6010 for all warranty issues All warranty parts will be shipped fre...

Reviews: