This device is a product of the KNX/EIB instabus-KNX/
EIB system and complies with KNX directives. Detailed
technical knowledge obtained in KNX/EIB training cour-
ses is a prerequisite to proper understanding.The func-
tionality of this device depends on the software.
Detailed information on loadable software and attainab-
le functionality as well as the software itself can be ob-
tained from the manufacturer's product database.
Planning, installation and commissioning of the unit is
effected by means of KNX-certified software. An up-
dated version of the product database and the technical
descriptions are available in the Internet at www.mer-
ten.de.
The coupler connects two instabus KNX/EIB data lines
and ensures the electrical separation of these lines
from one another. The definite functions of the device
are defined by addressing and parameterization.
Line coupler LK:
Physical address X.0.0
Connection of a main line (HL) with an area line (BL). Al-
ternatively with or without filter function. The coupler
belongs logically to the subordinate line.
Area coupler BK:
Physical address X.0.0
Connection of a main line (HL) with an area line (BL). Al-
ternatively with or without filter function. The coupler
belongs logically to the subordinate line.
Amplifier V:
Physical address X.Y.Z
Handling and repetition of telegrams on a line, no filter
function. Division of a line into max. 4 independent line
segments => max. 3 line amplifiers connected in paral-
lel per line (FIG. C). Each line segment requires a sepa-
rate power supply (SV) including a choke (DR).
EIB-System Information
What you can do with the Area/Line
Coupler
Schematics of an instabus KNX/EIB system
Use as area and line coupler (BK and LK)
Use as line coupler LK and amplifier V
(TLN = bus subscriber, DR = choke, SV = instabus KNX/
EIB power supply)
Each line requires a separate power supply.
1
programming button
2
programming LED, red
3
operation LED, green
4
LED amber, incoming data on superordinate line
(HL)
5
LED amber, incoming data on subordinate line Li-
nie (UL)
6
diagnosis LED, red
7
connecting terminal for superordinate line (HL)
8
connecting terminal for subordinate line (UL)
Function of diagnosis LED ("DIAG") red
LED off:
Telegrams are filtered or blocked
(both directions)
LED on:
Telegrams are retransmitted
without being filtered (at least one
direction)
LED flashing:
error detected (as per error flags
in device)
Controls and indicators
TLN
TLN
TLN
SV
DR
LK
HL1
BK
SV
DR
TLN
TLN
TLN
SV
DR
LK
HL2
BK
BL
SV
DR
SV
DR
TLN
TLN
SV DR
V
HL
SV DR
TLN
TLN
V
SV DR
TLN
TLN
V
SV DR
TLN
TLN
LK
SV DR
(2)
(1)
(3)
(5)
(6)
(4)
RUN
HL
UL
DIAG
HL
UL
(8) (7)
Function of operation LED ("RUN") green
LED off:
device off,
no voltage on superordinate line
LED on:
device on,
voltage on both lines
LED flashing:
no voltage on subordinate line
1
The device is snap-fastened on the DIN rail until the
latch is heard to engage, with the connecting termi-
nals pointing downwards
2
The superordinate line is connected with the left-
hand terminal (terminal "HL"). This terminal sup-
plies power to the device electronics so that it is
possible to report a bus voltage failure of the sub-
ordinate via the superordinate line.
3
The subordinate line is connected to the right-hand
terminal (terminal "UL").
|
Removal info:
Do not lever out the connecting
termianal from below. Risk of shorting the bus
voltage which is not available during the short-cir-
cuit.
¼
Risk of fatal injury from electrical current.
All work carried out on the device may only be per-
formed by skilled electricians.
The country-specific regulations and the valid KNX
guidelines must be followed.
1
Load the physical address into the push-button from
the ETS via the KNX bus.
2
Complete the required configuration settings in the
ETS, and transfer the configuration via EIB into the
coupler.
Supply
instabus KNX/EIB:
21 - 30 V DC
from superordinate line
Current consumption
superordinate line:
approx. 6 mA
subordinate line:
approx. 8 mA
Connection: KNX/EIB
instabus
terminal
for superordinate and
subordinate line
Fitting:
snap-fastening on DIN
rail
Ambient temperature:
-5 °C ... +45 °C
Storage temperature.:
-25 °C ... + 70 °C
Type of protection:
IP 20 in acc. with
EN 60529
Safety class:
III in acc. with
EN 61140
Installation width:
36 mm (2 modules)
Weight:
approx. 90 g
Merten GmbH & Co. KG,
Solutions for intelligent buildings
Service Center, Fritz-Kotz-Straße 8,
Industriegebiet Bomig-West
D-51674 Wiehl
Phone: +49
2261
702-204
Fax: +49
2261
702-136
E-Mail:
Internet: www.merten.de
InfoLine:
Phone:
+49 1805 212581* or +49 800 63783640
Fax:
+49 1805 212582* or +49 800 63783630
E-Mail:
* fee required
How to install the
Area/Line Coupler
How to set up the Area/Line Coupler
Technical data
Area/Line Coupler REG-K
Operating instructions
Art.-Nr. 680204
RUN
HL
UL
DIAG
HL
UL
V68
02-
582
-0
0
08/
06