Interface function (KNXnet/IP tunnelling)
The KNX/IP router can be used as an interface to the
KNX. The KNX can be accessed from any point in the
LAN. A second physical address must be assigned for
this purpose.
With version 0C and higher (see the back of the device),
a total of up to 5 simultaneous connections is supported.
Further information can be found in the application de-
scription.
A
Connecting terminals for external power supply
B
Bus connecting terminal
C
Programming button
D
Programming LED (red)
E
Operating LED KNX (green)
– LED lights up: bus voltage present
– LED blinking: telegram traffic
F
Operating LED Ethernet (green)
– LED lights up: Ethernet connection present
– LED blinking: telegram traffic
G
RJ45 socket for Ethernet connection
Connections, displays and operating
elements
G
E
F
A
B
C
D
¼
WARNING
Risk of death from electric shock. The device
can be damaged.
Safety clearance must be guaranteed in accord-
ance with IEC 60664-1. There must be at least 4
mm between the individual cores of the 230 V
supply cable and the KNX line
A
.
Mounting the device on the DIN rail
Connecting the device
1
Connect KNX.
2
Connect the Ethernet cable.
3
Connect the external power supply (only necessary
when power over Ethernet is not available).
1
Press the programming button.
The programming LED lights up.
2
Load the physical address and application into the
device from the ETS.
The programming LED goes out.
The operational LED lights up: the application has been
loaded successfully and the device is operative.
With version 0C and higher (see the back of the device),
you can assign other physical addresses directly on the
device. To do so, press the programming button for more
than 1 second.
Further information can be found in the application de-
scription.
Installing the KNX/IP router
Putting the KNX/IP router into
operation
230 V
4 mm
A
2
1
3
Gothaer Straße 29, 40880 Ratingen
www.merten.com
www.merten-austria.at
Customer care centre:
Technical data
Supply voltage
External power supply
via connecting termi-
nals:
AC 12-24 V
DC 12-30 V (SELV),
10 mA
Alternative power sup-
ply via RJ 45 socket:
Power over Ethernet (IEEE
802.3af)
Power consumption: max. 800 mW
Operating elements:
1x programming button
Display elements:
1x LED (red): programming
1x LED (green): KNX
1x LED (green): Ethernet
Connections
KNX:
Bus connecting terminal
Ethernet:
RJ45 socket
External power sup-
ply:
Screw terminals for cross-sec-
tions up to max. 2x 1.5 mm
2
Ambient temperature:
Operation:
-5 °C to +45 °C
Environment:
Can be used at elevations up
to 2000 m above sea level
(MSL)
Max. humidity:
93%, no condensation
Dimensions (HxWxD): 90x36x60 mm
Device width:
2 modules = 36 mm