e) Optimal Program :
The optimal program operates with many step configurations:
1.1.1.1.1
1.2.2.2.2
1.2.4.4.4
1.2.4.8.8
1.1.2.2.2
1.1.2.3.3
1.1.2.4.4
1.2.3.3.3
1.2.3.4.4
1.2.3.6.6
The target cos
power is reached using the fewest number of steps in minimal time. Like the
circular program, this algorithm equalises the usage of steps.
This program uses optimally selected steps sizes when approaching the target power and at
the same time the response delays are shortened, particularly if there is a large requirement for
kvar or if the network suddenly becomes capacitive.
Comparison between normal and optimal program:
Normal program will reach the cos
target value by successive connection/disconnection of
kvar corresponding to the smallest step value.
Optimal program will reach the target cos
value by successive connection/disconnection of
kvar corresponding to the highest relevant and available step value
Figure 20: Circular B program -
Operation sequence 1:2:2
Figure 19: Circular A program - Operation
sequence 1:1:1
Step
Step number
demand 1 2 3 4 5 6
+ X
+ X X
+ X X X
+ X X X X
- X X X
- X X
+ X X X
+ X X X X
- X X X
- X X
+ X X X
+ X X X X
- X X X
Step
Step number
demand 1 2 3 4 5 6
+ X
+ X X
+ X X X
- X X
+ X X X
+ X X X X
- X X X
- X X
- X
+ X X
+ X X X
+ X X X X
+ X X X X X
- X X X X
- X X X
- X X
Summary of Contents for Varlogic NR12
Page 1: ...Varlogic NR6 NR12 Power factor controller User manual...
Page 12: ...12 USER S MANUAL Figure 9 Bank pre configuration...
Page 16: ...16 USER S MANUAL Figure 12 Manual setup of parameters...
Page 21: ...21 USER S MANUAL Figure 16 1 Maintenance menu...
Page 22: ...22 USER S MANUAL Figure 16 2 Maintenance menu...
Page 28: ...28 USER S MANUAL Figure 23 HV use of the controller...